2014-11-06 14:22:09 | 11/6/2014 |
| PROJECT: ZOECKLER |
| PERMIT#: 14070538 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 3RD ELECTRICAL PLAN REVIEW |
| ACTION: PROVISO |
| |
| 1) IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS |
| REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE |
| 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY |
| BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE |
| NO OTHER OUTLETS. NEC 210.11(C)(3) REVISE PANEL |
| SCHEDULE AND ELECTRICAL FLOOR PLAN TO INDICATE THE |
| REQUIRED 20AMP BRANCH CIRCUIT FOR THE BATHROOMS. |
| |
| 2) RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT |
| MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL |
| SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE |
| OUTLET. NEC 210.52 (A)(1) REVISE ELECTRICAL FLOOR PLAN |
| TO COMPLY WITH 210.52 |
| |
| 3) A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER. |
| RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT |
| ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.) |
| MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT |
| SPACE. NEC210.52(C)(1) REVISE ELECTRICAL FLOOR PLAN TO |
| COMPLY WITH 210.52 |
| |
| 4) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1) |
| THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| PROTECTION FOR PERSONNEL. NEC 210.8(A) (1) |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |