Plan Review Notes For Permit 14070538 |
Permit Number |
14070538 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-11-01 03:43:50 | 1) THE SANITARY IS NOT DRAWN TO CODE. SUBMIT A | | COMPLETELY NEW CODE COMPLIANT RISER DIAGRAM FOR REVIEW | | . WPB AMEND. TO 2010 FBC SEC.107.3.5.3. | | 2) 2010 FBCR SEC. P3104.3 - EVERY DRY CONNECTING TO A | | HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF | | THE HORIZONTAL DRAIN PIPE. | | 3) THE PLUMBING FIXTURES SHALL BE VENTED PER THE 2010 | | FBCR SEC.P3101.2, P3101.2.1. | | 4) CLEANOUTS ARE REQUIRED IN ALL STACKS. 2010 FBCR | | SEC.P3005.2.6. | | 5) A CLEANOUT IS REQUIRED AT THE BUILDING DRAIN AND | | BUILDING SEWER PER THE 2010 FBCR SEC.P3005.2.7. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|