2014-09-09 07:25:35 | PLAN REVIEW COMMENTS |
| |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| ELECTRICAL |
| |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) FBC- 107.3.5.3 - ELECTRIC SERVICE RISER WITH WIRE |
| SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE |
| LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON |
| FLOOR PLAN. |
| |
| 2) FBC- 107.3.5.3 - PROVIDE SMOKE DETECTORS PURSUANT TO |
| FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| |
| 3) NEC 240.24(A) & (B) PANELS SHALL BE READILY |
| ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS. |
| SPECIFY THE LOCATIONS OF THE PANELS ON THE ELECTRICAL |
| FLOOR PLAN. |
| |
| 4) THE PLANS SHOW THAT THERE ARE TWO METERS ON THE |
| BUILDING ( ONE FOR EACH UNIT). THE PANEL SCHEDULE IS |
| LABELED AS 150 AMP AND THE RISER HAS THE PANEL AS 200 |
| AMP. PLEASE CLARIFY. |
| |
| 5) NEC 210.52(A) - (H) RECEPTACLE OUTLET SPACING, IT |
| APPEARS SOME POINTS ALONG THE WALL EXCEED 6' FROM AN |
| OUTLET, KITCHEN COUNTER TOP RECEPTACLE SPACING IS NOT |
| ADEQUATE, OUTDOOR RECEPTACLE OUTLETS ARE REQUIRED AT |
| THE FRONT AND BACK OF EACH DWELLING UNIT. |
| |
| 6) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET |
| FOR WITHIN 25' OF MECHANICAL EQUIPMENT. |
| |
| 7) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH |
| CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| OUTLETS. |
| |
| 8) NEC 210.12(B) - OUTLETS TO BE AFCI PROTECTED. |
| |
| 9) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| REQUIRED. |
| |
| 10) NEC 250.56 - SERVICE GROUNDING ELECTRODE TO BE |
| AUGMENTED BY AN ADDITIONAL ELECTRODE 6 FEET AWAY OR |
| PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR |
| LESS. |
| |
| 11) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL |
| BE PROVIDED. |
| |
| 12) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE |
| PRESENT. |
| |
| 13) NEC 210.8 (A)(1)-(8) - GROUND-FAULT |
| CIRCUIT-INTERRUPTER PROTECTION REQUIRED. |
| |
| 14) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE |
| REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE |
| PLANS. |
| |
| 15) NEC 210.70 (A) - (C) LIGHTING OUTLETS REQUIRED. AT |
| LEAST ONE WALL SWITCH CONTROLLED LIGHTING OUTLET IS |
| REQUIRED ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR |
| EXITS. |
| |
| IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |