Plan Review Notes
Plan Review Notes For Permit 14070508
Permit Number 14070508
Review Stop B
Sequence Number 1
Notes
Date Text
2014-07-23 10:06:50BUILDING PLAN REVIEW
 REVISION: 14070508
 PERMIT: 13090635
 ADD: 882 MALCOLM CHANDLIER LN.
 CONT: KAST
 TEL: (561)346-4994
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 23/2014
 ACTION: DENIED
  
 1) THE CONCRETE MIX DESIGN FOR COLUMNS DOES NOT MATCH
 THAT OF THE PLANS. 13090635 BLDG # 1 DESIGN MIX FOR ALL
 BUILDINGS SEE SHEET S-3 NOTES CONCRETE NOTES FOR
 COLUMNS, BEAMS & TIE BEAMS INDICATE A 4000 PSI MIX. THE
 SUBMITTAL SHOWS ONM & J, S REQUIREMENT FOR A 4,000 PSI
 MIX ON THE COVER SHEET THEN CROSSED THROUGH AND WORDS"
 RFI TO BE WRITTEN". A REVISION WILL BE REQUIRED FOR THE
 PLANS AND CALCULATIONS FOR THE REDUCTION IN STRENGTH OF
 THE STRUCTURAL ELEMENTS. 2010 FBC-B 1905.2 SELECTION OF
 CONCRETE PROPORTIONS. CONCRETE PROPORTIONS SHALL BE
 DETERMINED IN ACCORDANCE WITH THE PROVISIONS OF ACI
 318, SECTION 5.2.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  