Plan Review Notes For Permit 14070507 |
Permit Number |
14070507 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-07-28 12:45:48 | DATE: 7/28/2014 | | PROJECT: TOYS R US .PBOM E115 | | PERMIT#: 14070507 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY | | AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS | | THAT SERVING THE NORMAL LIGHTING IN THE AREA AND | | CONNECTED AHEAD OF ANY LOCAL SWITCHES NEC 701.11(G) | | | | 2) ADDITIONAL SHEETS SUBMITTED ARE WITHOUT ENGINEER'S | | SIGNATURE OR SEAL. ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | DESIGN. FBC 107.2.1 | | | | 3) BASED ON THE OVERALL SCOPE OF WORK ON THE PLANS | | SUBMITTED FOR REVIEW THE VALUATION INDICATED ON THE | | PERMIT APPLICATION IS LOW. PLEASE PROVIDE ADDITIONAL | | CONFIRMATION OF THE SCOPE OF WORK AND VALUATION OF SAME | | IN THE FORM OF A CONTRACT OR SOME OTHER WRITTEN | | VERIFIABLE EVIDENCE OF VALUE. FBC WPB AMENDMENTS. | | SECTION 109.3 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|