2014-09-08 14:41:11 | DATE: 9/8/2014 |
| PROJECT: 437 WILDER |
| PERMIT#: 14070494 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) DETERMINE THE LOCATION OF THE ELECTRICAL PANEL. |
| THERE ARE CURRENTLY 2 PANEL LOCATIONS IN THE GARAGE AND |
| ONLY ONE PANEL SCHEDULE. REVISE PLANS ACCORDINGLY. |
| |
| 2) PROVIDE A MAIN SERVICE DISCONNECT AT A READILY |
| ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF |
| THE SERVICE CONDUCTORS. NEC 230.70 REVISE PLANS TO |
| INDICATE ONLY ONE MAIN BREAKER PANEL ON THE EXTERIOR |
| WALL NEAREST THE POIUNT OF SERVICE ENTRANCE. |
| |
| 3) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION |
| FOR PERSONNEL. ALL OUTLETS IN THE GARAGE SHALL BE GFCI |
| PROTECTED. NEC 210.8. INCLUDING THE GDO |
| |
| 4) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE AND CARBON |
| MONOXIDE ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| FBC-RESIDENTIAL 314 AND 315. INCICATE C/O DETECTORS |
| WITHIN 10' FROM SLEEPING AREAS |
| |
| 5) 210.52(C) COUNTERTOPS. IN KITCHENS, PANTRIES, |
| BREAKFAST ROOMS, DINING ROOMS, AND SIMILAR AREAS OF |
| DWELLING UNITS, RECEPTACLE OUTLETS FOR COUNTERTOP |
| SPACES SHALL BE INSTALLED IN ACCORDANCE WITH |
| 210.52(C)(1) THROUGH (C)(5). PROVIDE ADDITIONAL GFI |
| OUTLETS IN THE KITCHEN. |
| |
| 6) INDICATE ON THE PLANS CEILING FANS SHALL BE |
| SUPPORTED IN ACCORDANCE WITH THE NEC 314.27 |
| |
| 7) INDICATE SUFFICIENT ACCESS AND WORKING SPACE SHALL |
| BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL |
| EQUIPMENT TO PERMIT READY AND SAFE OPERATION AND |
| MAINTENANCE OF SUCH EQUIPMENT. REVISE PLANS TO RELOCATE |
| A/C DISCONNECTS OUT FROM BEHIND A/C UNITS IN ACCORDANCE |
| WITH NEC 110.26 |
| |
| 8) REVISE THE RISER DIAGRAM TO ELIMINATE THE GROUNDING |
| CONDUCTOR FROM THE CONDUIT BETWEEN THE METER AND THE |
| MAIN DISCONNECT IN THE PANEL. 250.24 (C) GROUNDED |
| CONDUCTOR BROUGHT TO SERVICE EQUIPMENT. |
| |
| 9) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING |
| INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED |
| FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO |
| ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE |
| DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR |
| STRUCTURES. NEC 250.94. INDICATE ON PLANS THE REQUIRED |
| INTERSYSTEM BOND STRIP IN ACCORDANCE WITH 250.94 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |