Plan Review Notes
Plan Review Notes For Permit 14070494
Permit Number 14070494
Review Stop E
Sequence Number 1
Notes
Date Text
2014-09-08 14:41:11DATE: 9/8/2014
 PROJECT: 437 WILDER
 PERMIT#: 14070494
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) DETERMINE THE LOCATION OF THE ELECTRICAL PANEL.
 THERE ARE CURRENTLY 2 PANEL LOCATIONS IN THE GARAGE AND
 ONLY ONE PANEL SCHEDULE. REVISE PLANS ACCORDINGLY.
  
 2) PROVIDE A MAIN SERVICE DISCONNECT AT A READILY
 ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF
 THE SERVICE CONDUCTORS. NEC 230.70 REVISE PLANS TO
 INDICATE ONLY ONE MAIN BREAKER PANEL ON THE EXTERIOR
 WALL NEAREST THE POIUNT OF SERVICE ENTRANCE.
  
 3) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. ALL OUTLETS IN THE GARAGE SHALL BE GFCI
 PROTECTED. NEC 210.8. INCLUDING THE GDO
  
 4) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE AND CARBON
 MONOXIDE ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315. INCICATE C/O DETECTORS
 WITHIN 10' FROM SLEEPING AREAS
  
 5) 210.52(C) COUNTERTOPS. IN KITCHENS, PANTRIES,
 BREAKFAST ROOMS, DINING ROOMS, AND SIMILAR AREAS OF
 DWELLING UNITS, RECEPTACLE OUTLETS FOR COUNTERTOP
 SPACES SHALL BE INSTALLED IN ACCORDANCE WITH
 210.52(C)(1) THROUGH (C)(5). PROVIDE ADDITIONAL GFI
 OUTLETS IN THE KITCHEN.
  
 6) INDICATE ON THE PLANS CEILING FANS SHALL BE
 SUPPORTED IN ACCORDANCE WITH THE NEC 314.27
  
 7) INDICATE SUFFICIENT ACCESS AND WORKING SPACE SHALL
 BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL
 EQUIPMENT TO PERMIT READY AND SAFE OPERATION AND
 MAINTENANCE OF SUCH EQUIPMENT. REVISE PLANS TO RELOCATE
 A/C DISCONNECTS OUT FROM BEHIND A/C UNITS IN ACCORDANCE
 WITH NEC 110.26
  
 8) REVISE THE RISER DIAGRAM TO ELIMINATE THE GROUNDING
 CONDUCTOR FROM THE CONDUIT BETWEEN THE METER AND THE
 MAIN DISCONNECT IN THE PANEL. 250.24 (C) GROUNDED
 CONDUCTOR BROUGHT TO SERVICE EQUIPMENT.
  
 9) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED
 FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
 ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES. NEC 250.94. INDICATE ON PLANS THE REQUIRED
 INTERSYSTEM BOND STRIP IN ACCORDANCE WITH 250.94
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  