2015-03-10 18:39:46PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE NON
 IMPACT RATED SINGLE HUNG WINDOWS HAS DESIGN PRESSURES
 OF =/- 50 PSF. WINDOW #1 AND #3 REQUIRE HIGHER DESIGN
 PRESSURES(-65.0 AND -51.2 PSF) BASED ON THE REQUIRED
 PRESSURES IN THE SCHEDULE ON SHEET 3.1.
  
 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS THAT HAVE
 BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD AS
 REQUIRED BY DCA RULE 9N-3 AND FBC 107.3.4.1 FOR DOOR #2
 (WITH GLASS INSERT) THAT IS LISTED IN THE DOOR SCHEDULE
 ON SHEET 3.1
  
 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS THAT HAVE
 BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD AS
 REQUIRED BY DCA RULE 9N-3 AND FBC 107.3.4.1 FOR THE
 FIXED GLASS PICTURE WINDOW AND THE STRUCTURAL MULLIONS.
  
 4) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN
 INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING THE SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
  
  