Plan Review Notes For Permit 14070493 |
Permit Number |
14070493 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-08-14 19:06:43 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE PLANS SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. CITY AMENDMENTS | | 107.2.1 | | | | 2) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | NEW EXTERIOR DOORS AND WINDOWS AS REQUIRED BY DCA RULE | | 9N-3. | | | | 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY | | AMENDMENTS 107.3.4.1 | | | | 4) SHOW COMPLIANCE WITH FBC R301.2.1.2 FOR IMPACT | | PROTECTION OF GLAZED OPENINGS. | | | | 5) SECTION DETAILS ON SHEET 3.2 NEED CORRECTIONS. ITEM | | 13 ON DETAIL 6 IS A HEADER NOT A 2 X 6 BUCK. THE WALL | | FRAMING IS SPECIFIED AS 2 X 4. PLEASE REVIEW DETAIL 2 | | AND 6 ON SHEET 3.2 FOR MISTAKES. CITY AMENDMENTS | | 107.2.1 | | | | 6) THE ELECTRICAL NOTES ON THE UN-NUMBERED SHEET | | REFERENCES THE WRONG NFPA CODE EDITIONS. THE 2010 FBC | | REFERENCES NFPA-70 2008, NFPA-72 2007 AND NFPA-101 | | 2006. PLEASE CORRECT. | | | | 7) ON SHEET 3.1 THE WINDLOAD PRESSURES IN THE SCHEDULE | | ARE FOR AN EFFECTIVE WIND AREA OF 10 SQFT AND THE | | SCHEDULE HAS 50 SQFT. THE CORNER DISTANCE "A" IS 4 FEET | | IN ALL CASES AND 3 FEET IS SPECIFIED ON THE SCHEDULE. | | PLEASE CORRECT. FBCR301.2.1 AND FIGURE R301.2(7) | | | | 8) THE PRESSURES IN THE WINDOW AND DOOR SCHEDULE ARE | | HIGHER THAN THE WORST CASE PRESSURES THAT ARE LISTED IN | | THE WINDLOAD SCHEDULE. PLEASE CORRECT. FBCR301.2.1 AND | | CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|