Date |
Text |
2014-07-30 09:02:20 | DATE: 7/21/2014 |
| PROJECT: AMOWITZ REPAIR |
| PERMIT#: 14070448 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| SEVERAL COMMENTS ARE DUPLICATED FROM PREVIOUS REVIEW. |
| |
| 1) PLANS AND NOTES ARE CONFLICTING. THE NOTES AND |
| APPLICATION INDICATE COMPLETE REWIRING CONFORMING TO |
| ALL CURRENT FBC AND NEC BUT THE FLOORPLAN LAYOUT DO NOT |
| CONFORM TO CODE. RE-SUBMIT WITH THE ACTUAL LOCATIONS OF |
| THE ELECTRICAL SERVICE THE MAIN DISCONNECTING MEANS, |
| THE ELECTRICAL PANEL, AS WELL AS ALL SWITCHES AND |
| OUTLETS AS REQUIRED BY NEC 210.52, SMOKE DETECTORS, A/C |
| EQUIPMENT APPLIANCES, WASHER DRYER WATER HEATER, AND |
| ANY AND ALL ELECTRICAL UTILITY DEVICES AND EQUIPMENT TO |
| BE INSTALLED. FBC 107.2.1. SECOND SUBMITTAL STILL |
| CONFUSING AND NOT CODE COMPLIANT AS STATED. |
| |
| 2) AN INTER-SYSTEM BONDING TERMINATION FOR CONNECTING |
| INTER-SYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED |
| FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO |
| ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE |
| DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR |
| STRUCTURES. NEC 250.94. NOTED ON THE PLAN NOTES BUT NOT |
| INDICATED ON THE PLAN. |
| |
| 3) THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED |
| AT A READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A |
| BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF |
| ENTRANCE OF THE SERVICE CONDUCTORS. NEC 230.70(A)(1) |
| THIS IS WHY THE LOCATION OF THE MAIN DISCONNECTING |
| MEANS IS REQUIRED TO BE INDICATED ON THE PLANS. SECOND |
| SUBMITTAL STILL NOT INDICATED. THE RISER DIAGRAM |
| APPEARS TO CONFLICT WITH THIS NOTE. THE PANEL SCHEDULE |
| INDICATES THE PANEL IS EXISTING. IDENTIFY THE LOCATION |
| OF THE EXISTING ELECTRICAL PANEL AND THE ELECTRICAL |
| SERVICE ON THE FLOOR PLAN. |
| |
| 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 A FAULT CURRENT CALCULATION IS |
| REQUIRED. |
| |
| 5) THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT |
| BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH |
| CIRCUITS SUPPLIED. NEC 220.40. PROVIDE A LOAD |
| CALCULATION IN COMPLIANCE WITH NEC ARTICLE 220 ACTUAL |
| LOAD CALCULATION REQUIRED BASED ON THE NEC ARTICLE 220. |
| 220.1 SCOPE. THIS ARTICLE PROVIDES REQUIREMENTS FOR |
| CALCULATING BRANCH-CIRCUIT, FEEDER, AND SERVICE LOADS. |
| PART I PROVIDES FOR GENERAL REQUIREMENTS FOR |
| CALCULATION METHODS. PART II PROVIDES CALCULATION |
| METHODS FOR BRANCH-CIRCUIT LOADS. PARTS III AND IV |
| PROVIDE CALCULATION METHODS FOR FEEDERS AND SERVICES. |
| FABRICATING A TOTAL CONNECTED ELECTRICAL DEMAND BASED |
| ON A PARTIAL PANEL SCHEDULE IS NOT AN APPROVED METHOD. |
| |
| 6) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI |
| PROTECTED. NEC 210.12. NEW RECEPTACLES MUST BE TAMPER |
| RESISTANT. NEC 406.11 NOTED ON PLANS. |
| |
| 7) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE |
| BATHROOMS. NEC 210.11 (C) SECOND SUBMITTAL STILL DOES |
| NOT INDICATE A BATHROOM OUTLET ON THE PLANS. |
| |
| 8) ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 |
| FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 |
| FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 NOTED ON |
| PLANS. |
| |
| 9) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS |
| APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON |
| MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| ROOM USED FOR SLEEPING. 2010 FBC R314, 315 SECOND |
| SUBMITTAL STILL DOES NOT INDICATE INTER-CONNECTED |
| SMOKE/CO DETECTORS ON THE PLANS. |
| |
| 10) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE |
| SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE |
| LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS |
| SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT |
| CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32 |
| KG (70 LB). FOR OUTLET BOXES OR OUTLET BOX SYSTEMS |
| DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) FANS |
| THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED |
| MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE |
| SUPPORTED. NEC 314(D) BOXES AT CEILING-SUSPENDED |
| (PADDLE) FAN OUTLETS. NOTED ON PLANS. |
| |
| 11) EACH DISCONNECTING MEANS SHALL BE LEGIBLY MARKED TO |
| INDICATE ITS PURPOSE UNLESS LOCATED AND ARRANGED SO THE |
| PURPOSE IS EVIDENT. THE MARKING SHALL BE OF SUFFICIENT |
| DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. NEC |
| 110.22 (A) INDICATE THE LOCATIONS AND DISCONNECTING |
| MEANS FOR MECHANICAL EQUIPMENT. A/C CU'S AND A/C AHU'S |
| |
| 12) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO |
| GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL |
| EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR |
| MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES. |
| NEC 110.33(B) |
| |
| 13) FOR ATTICS, UNDERFLOOR SPACES, UTILITY ROOMS, AND |
| BASEMENTS, AT LEAST ONE LIGHTING OUTLET CONTAINING A |
| SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE |
| INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR |
| CONTAIN EQUIPMENT REQUIRING SERVICING. AT LEAST ONE |
| POINT OF CONTROL SHALL BE AT THE USUAL POINT OF ENTRY |
| TO THESE SPACES. THE LIGHTING OUTLET SHALL BE PROVIDED |
| AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. NEC |
| 210.70(3) |
| |
| 14)THE PROVISIONS OF PART II ARE INTENDED TO REQUIRE |
| DISCONNECTING MEANS CAPABLE OF DISCONNECTING |
| AIR-CONDITIONING AND REFRIGERATING EQUIPMENT, INCLUDING |
| MOTOR-COMPRESSORS AND CONTROLLERS FROM THE CIRCUIT |
| CONDUCTORS. NEC 440.11 |
| |
| 15) DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT |
| FROM AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING |
| OR REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS |
| SHALL BE PERMITTED TO BE INSTALLED ON OR WITHIN THE |
| AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14 |
| |
| 16) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI |
| RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| LOCATION FOR THE SERVICING OF HEATING, |
| AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE |
| RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND |
| REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL |
| NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT |
| DISCONNECTING MEANS. NEC 210.63 SEE 210.8(A)(3), |
| ALL 15 AND 20AMP, 125V AND 250V RECEPTACLES INSTALLED |
| IN IN A WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS |
| WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS |
| INSERTED. ALL 15- AND 20-AMPERE, 125- AND 250-VOLT |
| NON-LOCKING RECEPTACLES SHALL BE LISTED |
| WEATHER-RESISTANT TYPE. NEC 406.8(B)(1) |
| |
| 17) NEW OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT |
| MUST NOW HAVE A RECEPTACLE OUTLET (GFCI PROTECTED) NEC |
| (210.52(E)(3). |
| |
| 18) UTILITY ROOM OUTLET SHOWN ON PLANS IS REQUIRED O BE |
| GFCI PROTECTED. 210.8(C)(2) |
| |
| 19) LAUNDRY BRANCH CIRCUITS IN ADDITION TO THE NUMBER |
| OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS |
| SECTION, AT LEAST ONE ADDITIONAL 20-AMPERE BRANCH |
| CIRCUIT SHALL BE PROVIDED TO SUPPLY THE LAUNDRY |
| RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F). THIS |
| CIRCUIT SHALL HAVE NO OTHER OUTLETS. |
| |
| 20) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT |
| GRADE LEVEL AND LOCATED NOT MORE THAN 6.5' FT ABOVE |
| GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE |
| DWELLING. NEC 210.52(E)(3) |
| |
| THE ABOVE LISTED NOTES ONLY NAME A FEW. IF THE INTENT |
| OF THIS PERMIT APPLICATION AND ASSOCIATED CONSTRUCTION |
| DOCUMENTS IS TO COMPLY WITH THE PROVISIONS OF ALL |
| CURRENT CODES AND ORDINANCES PLEASE READ AND AND COMPLY |
| WITH THE PROVISIONS OF THE 2008 EDITION OF THE NATIONAL |
| ELECTRICAL CODE, AND THE 2010 EDITION OF THE FLORIDA |
| BUILDING CODE AS WELL AS THE WEST PALM BEACH AMENDMENTS |
| TO CHAPTER ONE OF THE FLORIDA BUILDING CODE. |
| |
| WHEN RESUMEITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND |
| LEAVE THE PREVIOUSLY REVIEWED SHEETS. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |