2014-07-30 09:02:20DATE: 7/21/2014
 PROJECT: AMOWITZ REPAIR
 PERMIT#: 14070448
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 SEVERAL COMMENTS ARE DUPLICATED FROM PREVIOUS REVIEW.
  
 1) PLANS AND NOTES ARE CONFLICTING. THE NOTES AND
 APPLICATION INDICATE COMPLETE REWIRING CONFORMING TO
 ALL CURRENT FBC AND NEC BUT THE FLOORPLAN LAYOUT DO NOT
 CONFORM TO CODE. RE-SUBMIT WITH THE ACTUAL LOCATIONS OF
 THE ELECTRICAL SERVICE THE MAIN DISCONNECTING MEANS,
 THE ELECTRICAL PANEL, AS WELL AS ALL SWITCHES AND
 OUTLETS AS REQUIRED BY NEC 210.52, SMOKE DETECTORS, A/C
 EQUIPMENT APPLIANCES, WASHER DRYER WATER HEATER, AND
 ANY AND ALL ELECTRICAL UTILITY DEVICES AND EQUIPMENT TO
 BE INSTALLED. FBC 107.2.1. SECOND SUBMITTAL STILL
 CONFUSING AND NOT CODE COMPLIANT AS STATED.
  
 2) AN INTER-SYSTEM BONDING TERMINATION FOR CONNECTING
 INTER-SYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED
 FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
 ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES. NEC 250.94. NOTED ON THE PLAN NOTES BUT NOT
 INDICATED ON THE PLAN.
  
 3) THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED
 AT A READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF
 ENTRANCE OF THE SERVICE CONDUCTORS. NEC 230.70(A)(1)
 THIS IS WHY THE LOCATION OF THE MAIN DISCONNECTING
 MEANS IS REQUIRED TO BE INDICATED ON THE PLANS. SECOND
 SUBMITTAL STILL NOT INDICATED. THE RISER DIAGRAM
 APPEARS TO CONFLICT WITH THIS NOTE. THE PANEL SCHEDULE
 INDICATES THE PANEL IS EXISTING. IDENTIFY THE LOCATION
 OF THE EXISTING ELECTRICAL PANEL AND THE ELECTRICAL
 SERVICE ON THE FLOOR PLAN.
  
 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9 A FAULT CURRENT CALCULATION IS
 REQUIRED.
  
 5) THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT
 BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH
 CIRCUITS SUPPLIED. NEC 220.40. PROVIDE A LOAD
 CALCULATION IN COMPLIANCE WITH NEC ARTICLE 220 ACTUAL
 LOAD CALCULATION REQUIRED BASED ON THE NEC ARTICLE 220.
 220.1 SCOPE. THIS ARTICLE PROVIDES REQUIREMENTS FOR
 CALCULATING BRANCH-CIRCUIT, FEEDER, AND SERVICE LOADS.
 PART I PROVIDES FOR GENERAL REQUIREMENTS FOR
 CALCULATION METHODS. PART II PROVIDES CALCULATION
 METHODS FOR BRANCH-CIRCUIT LOADS. PARTS III AND IV
 PROVIDE CALCULATION METHODS FOR FEEDERS AND SERVICES.
 FABRICATING A TOTAL CONNECTED ELECTRICAL DEMAND BASED
 ON A PARTIAL PANEL SCHEDULE IS NOT AN APPROVED METHOD.
  
 6) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12. NEW RECEPTACLES MUST BE TAMPER
 RESISTANT. NEC 406.11 NOTED ON PLANS.
  
 7) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE
 BATHROOMS. NEC 210.11 (C) SECOND SUBMITTAL STILL DOES
 NOT INDICATE A BATHROOM OUTLET ON THE PLANS.
  
 8) ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 NOTED ON
 PLANS.
  
 9) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315 SECOND
 SUBMITTAL STILL DOES NOT INDICATE INTER-CONNECTED
 SMOKE/CO DETECTORS ON THE PLANS.
  
 10) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE
 SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE
 LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS
 SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT
 CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32
 KG (70 LB). FOR OUTLET BOXES OR OUTLET BOX SYSTEMS
 DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) FANS
 THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED
 MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE
 SUPPORTED. NEC 314(D) BOXES AT CEILING-SUSPENDED
 (PADDLE) FAN OUTLETS. NOTED ON PLANS.
  
 11) EACH DISCONNECTING MEANS SHALL BE LEGIBLY MARKED TO
 INDICATE ITS PURPOSE UNLESS LOCATED AND ARRANGED SO THE
 PURPOSE IS EVIDENT. THE MARKING SHALL BE OF SUFFICIENT
 DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. NEC
 110.22 (A) INDICATE THE LOCATIONS AND DISCONNECTING
 MEANS FOR MECHANICAL EQUIPMENT. A/C CU'S AND A/C AHU'S
  
 12) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR
 MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES.
 NEC 110.33(B)
  
 13) FOR ATTICS, UNDERFLOOR SPACES, UTILITY ROOMS, AND
 BASEMENTS, AT LEAST ONE LIGHTING OUTLET CONTAINING A
 SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE
 INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR
 CONTAIN EQUIPMENT REQUIRING SERVICING. AT LEAST ONE
 POINT OF CONTROL SHALL BE AT THE USUAL POINT OF ENTRY
 TO THESE SPACES. THE LIGHTING OUTLET SHALL BE PROVIDED
 AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. NEC
 210.70(3)
  
 14)THE PROVISIONS OF PART II ARE INTENDED TO REQUIRE
 DISCONNECTING MEANS CAPABLE OF DISCONNECTING
 AIR-CONDITIONING AND REFRIGERATING EQUIPMENT, INCLUDING
 MOTOR-COMPRESSORS AND CONTROLLERS FROM THE CIRCUIT
 CONDUCTORS. NEC 440.11
  
 15) DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT
 FROM AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING
 OR REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS
 SHALL BE PERMITTED TO BE INSTALLED ON OR WITHIN THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14
  
 16) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
 DISCONNECTING MEANS. NEC 210.63 SEE 210.8(A)(3),
 ALL 15 AND 20AMP, 125V AND 250V RECEPTACLES INSTALLED
 IN IN A WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS
 WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS
 INSERTED. ALL 15- AND 20-AMPERE, 125- AND 250-VOLT
 NON-LOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE. NEC 406.8(B)(1)
  
 17) NEW OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT
 MUST NOW HAVE A RECEPTACLE OUTLET (GFCI PROTECTED) NEC
 (210.52(E)(3).
  
 18) UTILITY ROOM OUTLET SHOWN ON PLANS IS REQUIRED O BE
 GFCI PROTECTED. 210.8(C)(2)
  
 19) LAUNDRY BRANCH CIRCUITS IN ADDITION TO THE NUMBER
 OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE ADDITIONAL 20-AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY THE LAUNDRY
 RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F). THIS
 CIRCUIT SHALL HAVE NO OTHER OUTLETS.
  
 20) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT
 GRADE LEVEL AND LOCATED NOT MORE THAN 6.5' FT ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING. NEC 210.52(E)(3)
  
 THE ABOVE LISTED NOTES ONLY NAME A FEW. IF THE INTENT
 OF THIS PERMIT APPLICATION AND ASSOCIATED CONSTRUCTION
 DOCUMENTS IS TO COMPLY WITH THE PROVISIONS OF ALL
 CURRENT CODES AND ORDINANCES PLEASE READ AND AND COMPLY
 WITH THE PROVISIONS OF THE 2008 EDITION OF THE NATIONAL
 ELECTRICAL CODE, AND THE 2010 EDITION OF THE FLORIDA
 BUILDING CODE AS WELL AS THE WEST PALM BEACH AMENDMENTS
 TO CHAPTER ONE OF THE FLORIDA BUILDING CODE.
  
 WHEN RESUMEITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,