Plan Review Notes For Permit 14070442
Permit Number 14070442
Review Stop E
Sequence Number 1
Notes
Date Text
2014-07-15 08:31:47DATE: 7/14/2014
 PROJECT: REWIRE DUPLEX
 PERMIT#: 14070442
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) IDENTIFY CIRCUITRY ON FLOOR PLAN. FBC 107.2.1
  
 2) PROVIDE PANEL SCHEDULE FOR EACH APT. FBC 107.2.1
  
 3) PROVIDE REVISED LOAD CALCULATION TO INCLUDE 2
 KITCHEN APPLIANCE CIRCUITS FOR EACH DWELLING UNIT AND
 TOTAL SQUARE FOOTAGE OF BOTH UNITS. NEC 220. FEEDER
 CONDUCTORS SHALL HAVE AN AMPACITY NOT
 LESS THAN REQUIRED TO SUPPLY THE LOAD AS CALCULATED IN
 PARTS III, IV, AND V OF ARTICLE 220. THE MINIMUM
 FEEDER-CIRCUIT CONDUCTOR SIZE, BEFORE THE APPLICATION
 OF ANY ADJUSTMENT OR CORRECTION FACTORS, SHALL HAVE AN
 ALLOWABLE AMPACITY NOT LESS THAN THE NONCONTINUOUS LOAD
 PLUS 125 PERCENT OF THE CONTINUOUS LOAD.
  
 4) PROVIDE REVISED RISER DIAGRAM TO INDICATE THE ACTUAL
 INSATLLATION PROPOSED. IDENTIFY EACH METER WITH THE
 CORRECT ADDRESS AND EACH MAIN WITH THE UNIT # IT FEEDS.
 INDICATE ON THE RISER THE LOCATION OF THE LOAD CENTERS.
 NEC 215.5
  
 5) BACK TO BACK OUTLETS BETWEEN APTS. TO BE FIRE RATED.
  
 6) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12
  
 7) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 8) GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND
 REAR ELEVATIONS. NEC 210.8
  
 9) PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE
 BRANCH CIRCUITS. NEC 210.52
  
 10) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE
 BATHROOMS. NEC 210.11 (C)(3)
  
 11) A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE
 GROUND NEC 250.94
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WPCONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBMI
 TTAL_FORM_04132010.PDF.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]