2014-07-23 16:20:51 | PLUMBING PLAN REVIEW |
| PERMIT: 14070406 |
| ADD:101 N CLEMATIS ST SUITES 120 & 130 |
| CONT: CHANDLER |
| TEL: (561)791-6934 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED JULY 23/ 2014 |
| ACTION: DENIED |
| |
| 1) SHEET P3.1 DETAIL # 6 SHOWS A/C CONDENSATE BEING |
| DRAINED INTO A SANITARY DRAIN WITH A SINK TAIL PIECE |
| ADAPTOR FOR A DISHWASHER WASTE. |
| PLEASE PROVIDE COMPLIANCE WITH: |
| 2010 FBC-PLUMBING 314.2.1 CONDENSATE DISPOSAL. |
| CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL |
| BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED |
| PLACE OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM |
| HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT |
| LESS THAN ONE-EIGHTH UNIT VERTICAL IN 12 UNITS |
| HORIZONTAL (1-PERCENT SLOPE). CONDENSATE SHALL NOT |
| DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO |
| CAUSE A NUISANCE. AN APPROVED PLACE OF DISPOSAL IS ROOF |
| DRAINS, FRENCH DRAINS, ETC... |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |