2014-07-23 16:20:51PLUMBING PLAN REVIEW
 PERMIT: 14070406
 ADD:101 N CLEMATIS ST SUITES 120 & 130
 CONT: CHANDLER
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED JULY 23/ 2014
 ACTION: DENIED
  
 1) SHEET P3.1 DETAIL # 6 SHOWS A/C CONDENSATE BEING
 DRAINED INTO A SANITARY DRAIN WITH A SINK TAIL PIECE
 ADAPTOR FOR A DISHWASHER WASTE.
 PLEASE PROVIDE COMPLIANCE WITH:
 2010 FBC-PLUMBING 314.2.1 CONDENSATE DISPOSAL.
 CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL
 BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED
 PLACE OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM
 HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT
 LESS THAN ONE-EIGHTH UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (1-PERCENT SLOPE). CONDENSATE SHALL NOT
 DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS TO
 CAUSE A NUISANCE. AN APPROVED PLACE OF DISPOSAL IS ROOF
 DRAINS, FRENCH DRAINS, ETC...
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  