2014-07-23 16:13:23FUEL GAS PLAN REVIEW
 PERMIT: 14070406
 ADD:101 N CLEMATIS ST SUITES 120 & 130
 CONT: CHANDLER
 TEL: (561)791-6934
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED JULY 23/ 2014
 ACTION: DENIED
  
 1) SHEET P02 & P2.3 SHOW SOME GAS DETAILS, SHEET P3.1
 DETAIL # 4 SHOW A 120 GALLON GAS WATER HEATER. THE
 DETAIL SHOWS WHAT APPEARS TO BE A ONE STORY BUILDING,
 PLEASE NOTE THIS IS A 5 STORY BUILDING WITH RESIDENTIAL
 UNITS ABOVE. PLEASE PROVIDE COMPLIANCE WITH THE
 FOLLOWING:
  
 1A) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS
 CODE SEC. 502 THRU 505.
  
 1B) SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 1C) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304
  
 2) THE PLANS ALSO INDICATE (2) GAS DRIERS SHOW
 COMPLIANCE WITH:
  
 2A) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS
 CODE SEC. 502 THRU 505.
  
 2B) SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  
 2C) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2010 FUEL GAS CODE SEC. 304.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676