2014-07-21 10:38:05 | DATE: 7/21/2014 |
| PROJECT: KIKIMAZ DESIGN |
| PERMIT#: 14070365 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. FBC 107.2.1 SIGN |
| AND PRINT THE NAME OF THE DESIGNER ON THE PLANS AS |
| INDICATED ABOVE. |
| |
| 2) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING |
| INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED |
| FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO |
| ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE |
| DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR |
| STRUCTURES. NEC 250.94. INDICATE AND PROVIDE THE |
| REQUIRED INTERSYSTEM BONDING DEVICE AT THE SERVICE AS |
| INDICATED ABOVE. |
| |
| 3) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED |
| MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND |
| ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL |
| BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY |
| INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF |
| A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT |
| REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 INDICATE |
| AND PROVIDE THE REQUIRED EXIT AND EMERGENCY |
| ILLUMINATION AS IIDICATED ABOVE. |
| |
| 4) AN INDIVIDUAL DISCONNECTING MEANS SHALL BE PROVIDED |
| FOR EACH CONTROLLER AND SHALL DISCONNECT THE |
| CONTROLLER. THE DISCONNECTING MEANS SHALL BE LOCATED IN |
| SIGHT FROM THE CONTROLLER LOCATION. EACH DISCONNECTING |
| MEANS SHALL BE LEGIBLY MARKED TO INDICATE ITS PURPOSE |
| UNLESS LOCATED AND ARRANGED SO THE PURPOSE IS EVIDENT. |
| THE MARKING SHALL BE OF SUFFICIENT DURABILITY TO |
| WITHSTAND THE ENVIRONMENT INVOLVED.NEC 430.102,110.22 |
| (A) INDICATE AND PROVIDE DICONNECTS AS REQUIRED AND |
| INDICATED ABOVE. |
| |
| 5) EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| SHALL BE PROVIDED WITH AT LEAST ONE OUTLET IN AN |
| ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT |
| SPACE FOR SIGN OR OUTLINE LIGHTING SYSTEM USE. THE |
| OUTLET(S) SHALL BE SUPPLIED BY A BRANCH CIRCUIT RATED |
| AT LEAST 20 AMPERES THAT SUPPLIES NO OTHER LOAD. |
| SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED |
| ACCESSIBLE TO PEDESTRIANS. NEC 600.5. INDICATE AND |
| PROVIDE THE REQUIRED SIGN CIRCUIT AS INDICATED ABOVE. |
| |
| 6) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED |
| MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND |
| ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL |
| BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY |
| INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF |
| A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT |
| REQUIRES EMERGENCY ILLUMINATION. NEC 700.16. PROVIDE |
| AND INSTALL THE REQUIRED EXIT AND EMERGENCY LIGHTING AS |
| INDICATED ABOVE. |
| |
| 7) ILLUMINATION SHALL BE PROVIDED FOR ALL WORKING |
| SPACES ABOUT SERVICE EQUIPMENT, SWITCHBOARDS, |
| PANELBOARDS, OR MOTOR CONTROL CENTERS INSTALLED |
| INDOORS. ADDITIONAL LIGHTING OUTLETS SHALL NOT BE |
| REQUIRED WHERE THE WORK SPACE IS ILLUMINATED BY AN |
| ADJACENT LIGHT SOURCE OR AS PERMITTED BY 210.70(A)(1), |
| EXCEPTION NO. 1, FOR SWITCHED RECEPTACLES. IN |
| ELECTRICAL EQUIPMENT ROOMS, THE ILLUMINATION SHALL NOT |
| BE CONTROLLED BY AUTOMATIC MEANS ONLY. NEC 110.26(D) |
| PROVIDE AND INSTALL THE REQUIRED ILLUMINATION AS |
| INDICATED ABOVE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND |
| LEAVE THE PREVIOUSLY REVIEWED SHEETS. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |