2014-07-29 07:07:23BUILDING PLAN REVIEW
 PERMIT: 14070364
 ADD: 401 CLEMATIS ST
 CITY HALL PARKING GARAGE/ DIESEL FUEL STORAGE
 CONT: TBD
 TEL: VIVEK 794-1061
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 29/2014
 ACTION: BUILDING PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A-1.02 THE HOLE CORE DRILLED THROUGH THE 2ND
 FLOOR GARAGE FLOOR SLAB FOR DETERMINING THE FLOOR FIRE
 RESISTANCE IN HOURS IS TO BE PROTECTED. THE 2010 FBC-B
 713.4.1.1. THROUGH PENETRATIONS. THIS IS BUILDING TYPE
 IIB CONSTRUCTION, FLOOR REQUIRED FIRE RATING IS 2 HRS.
 2010 FBC-B 721.2.2.1.2.
  
 JAMES A. WITMER CBO