2014-08-01 10:29:44DATE: 8/1/2014
 PROJECT: CITY OF WPB PARKING GARAGE GENERATOR FUEL TANK
 REPLACEMENT
 PERMIT#: 14070364
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ADDITIONAL INFORMATION REQUEST. PLEASE PROVIDE A
 DETAILED RESPONSE FOR THE FOLLOWING REQUESTS. FBC WPB
 AMENDMENTS 107.3.5.1
 1A.- IDENTIFY THE CLASSIFICATION OF THE ZONE.
 1B.- AN ELECTRICAL DETAIL FOR THE RELOCATION OF THE
 LIGHTING. NOTE 4. ON SHEET A-1.01 STATES TO "REMOVE ALL
 EXISTING CEILING LIGHT FIXTURES, VERIFY EXPLOSIVE
 RESISTANT AND RE-INSTALL IN SIMILAR LOCATION". PROVIDE
 A REFLECTED CEILING PLAN AND AN ELECTRICAL PLAN THAT
 INDICATES HOW AND WHERE THE LIGHTING IS TO BE
 RELOCATED, CONNECTED AND SUPPORTED. INCLUDE ALL EXIT
 AND EMERGENCY LIGHTING. IDENTIFY THE CLASSIFICATION OF
 THE ENVIRONMENT AND THE WIRING METHODS TO BE
 IMPLEMENTED AND FIRE RATING TO BE MAINTAINED.
 1C.- AN ELECTRICAL DETAIL FOR THE RELOCATION OF THE
 LIGHT SWITCH. SHEET A-1.01 INDICATES A "RELOCATED LIGHT
 SWITCH" PROVIDE AN ELECTRICAL FLOOR PLAN THAT INDICATES
 HOW AND WHERE THE SWITCH IS TO BE RELOCATED, CONNECTED
 AND SUPPORTED. IDENTIFY THE CLASSIFICATION OF THE
 ENVIRONMENT AND THE WIRING METHODS TO BE IMPLEMENTED
 AND FIRE RATING TO BE MAINTAINED.
 1D.- AN ELECTRICAL DETAIL TO INDICATE THE REMOVAL,
 RELOCATION, AND REWIRING OF THE CONTROL WORING TO THE
 FUEL TANK MONITORING SYSTEM. PROVIDE AN ELECTRICAL
 FLOOR PLAN THAT INDICATES HOW AND WHERE THE CONTROLER
 IS TO BE RELOCATED, CONNECTED AND SUPPORTED. IDENTIFY
 THE CLASSIFICATION OF THE ENVIRONMENT AND THE WIRING
 METHODS TO BE IMPLEMENTED AND FIRE RATING TO BE
 MAINTAINED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  