Plan Review Notes
Plan Review Notes For Permit 14070321
Permit Number 14070321
Review Stop B
Sequence Number 3
Notes
Date Text
2015-05-11 18:50:46PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) DOOR #5 IN THE SCHEDULE ON SHEET 3.0 WHICH SEPARATES
 THE GARAGE FROM THE SECOND FLOOR IS REQUIRED TO COMPLY
 WITH FBC-R302.5.1
  
 2) THE PRODUCT APPROVAL REQUIRES THE RAS 117
 CALCULATIONS TO BE SIGNED AND SEALED BY A FLORIDA
 LICENSED ENGINEER, ARCHITECT OR CERTIFIED ROOFING
 CONSULTANT. SPECIFY WHICH ONE OF THE APPROVED ROOFING
 ASSEMBLIES LISTED IN THE PRODUCT APPROVAL FOR GAF
 MODIFIED ROOFING SYSTEM (NOA NO. 14-0102.12) WILL BE
 INSTALLED. IDENTIFY THE ANCHORING AND DESIGN PRESSURES
 FOR THE SELECTED ASSEMBLY. SUBMIT TWO SETS OF SIGNED
 AND SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING
 IF THE DESIGN PRESSURES ARE LESS THAN REQUIRED.
  
 3) SUBMIT 2 COPIES OF PRODUCT APPROVALS, KEY PLANS AND
 INSTALLATION SCHEDULES FOR THE IMPACT PROTECTION
 DEVICES THAT ARE REQUIRED FOR THE NON-IMPACT RATED
 SLIDING GLASS DOORS (NOA NO. 11-1201.03). DCA RULE 9N-3
 AND FBC 107.2.1
  
 4) THE PRODUCT APPROVAL SUBMITTED FOR THE LARGE MISSILE
 IMPACT RATED SINGLE HUNG WINDOWS HAS INSTALLATION
 DRAWINGS FOR WINDOWS WITH NO IMPACT RATING. THE FL
 NUMBER WRITTEN ON THE SUBMITTAL IS INCORRECT. IT IS
 MISSING A NUMBER AND SHOULD BE FL 14462. PLEASE
 CORRECT.
  
 5) THE INSTALLATION SCHEDULE THAT WAS SUBMITTED FOR THE
 STEEL STORM PANELS HAS THE GLASS SEPARATION INCORRECTLY
 SPECIFIED AS 3". SEE TABLE 2 ON SHEET 4 OF 4. FOR
 SYSTEM 3 WITH A PANEL LENGTH OF UP TO 8'-8" AND A
 POSITIVE PRESSURE OF UP TO 50 PSF, THE MINIMUM GLASS
 SEPARATION IS 3.5". PLEASE CORRECT.
  
  