2015-03-13 10:38:37PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE AN EQUIPMENT SCHEDULE FOR THE HEATING AND
 COOLING EQUIPMENT ON THE MECHANICAL PLANS THAT IS
 CONSISTENT WITH THE EQUIPMENT SIZING CALCULATIONS AND
 THE ENERGY COMPLIANCE FORM. PROVIDE THE MODEL NUMBERS
 FOR THE AIR HANDLER AND CONDENSING UNIT. CITY
 AMENDMENTS 107.2.1.3 AND 107.3.5.3 (REPEAT COMMENT)
  
 2) THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE IS
 REQUIRED ON THE PAPER PLANS THAT WERE SUBMITTED.
 DIGITAL SIGNATURES ARE FOR USE ON ELECTRONICALLY
 TRANSMITTED PLANS.
 SEE FS 471 & FS 668
  
  