2015-03-16 12:08:16 | PLAN REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE PLANS THAT WERE SUBMITTED HAVE AN ENGINEER'S |
| SEAL AND A DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE |
| ONLY VALID FOR ELECTRONICALLY TRANSMITTED PLANS. PLANS |
| THAT ARE SUBMITTED ON PAPER ARE REQUIRED TO HAVE THE |
| ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE ON THEM IN |
| ADDITION TO THEIR SEAL. FS 471 |
| |
| 2) THE TYPE OF CONSTRUCTION AND THE TYPE OF OCCUPANCY |
| SPECIFIED ON THE COVER SHEET ARE INCORRECT. THE |
| CONSTRUCTION TYPE SHOULD BE V-B AND THE OCCUPANCY TYPE |
| IS R-3. |
| FBC 601 AND 301 |
| |
| 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. THE ENGINEER, MANUEL MARTINEZ, IS |
| THE DESIGNER OF RECORD FOR THIS PROJECT. THE PRODUCT |
| APPROVALS WERE NOT APPROVED BY ENGINEER. |
| |
| 4) DOOR #5 IN THE SCHEDULE ON SHEET 3.0 WHICH SEPARATES |
| THE GARAGE FROM THE SECOND FLOOR IS REQUIRED TO COMPLY |
| WITH FBC-R302.5.1 |
| |
| 5) SPECIFY WHICH ONE OF THE APPROVED ROOFING ASSEMBLIES |
| LISTED IN THE PRODUCT APPROVAL FOR GAF MODIFIED ROOFING |
| SYSTEM (NOA NO. 14-0102.12) WILL BE INSTALLED. IDENTIFY |
| THE ANCHORING AND DESIGN PRESSURES FOR THE SELECTED |
| ASSEMBLY. SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 |
| CALCULATIONS FOR ENHANCED FASTENING IF THE DESIGN |
| PRESSURES ARE LESS THAN REQUIRED. |
| |
| 6) THE PRODUCT APPROVALS FOR THE OUT-SWING FRENCH DOORS |
| ( NOA NO. 08-0312.09 ) EXPIRED IN MAY 2011. SUBMIT |
| CURRENT PRODUCT APPROVALS. DCA RULE 9N-3 |
| |
| 7) SUBMIT PRODUCT APPROVALS FOR THE STUCTURAL MULLIONS |
| THAT WILL BE REQUIRED BETWEEN THE FRENCH DOORS AND THE |
| FIXED WINDOWS OR SUBMIT PRODUCT APPROVALS FOR FRENCH |
| DOORS WITH SIDELIGHTS. DCA RULE 9N-3 |
| |
| 8) SUBMIT 2 COPIES OF PRODUCT APPROVALS, KEY PLANS AND |
| INSTALLATION SCHEDULES FOR THE IMPACT PROTECTION |
| DEVICES THAT ARE REQUIRED FOR THE NON-IMPACT RATED |
| SLIDING GLASS DOORS (NOA NO. 11-1201.03). DCA RULE 9N-3 |
| AND FBC 107.2.1 |
| |
| 9) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| SECTIONAL GARAGE DOOR HAS A DESIGN PRESSURE OF -52.0 |
| PSF AND THE PLANS SEPCIFY THAT -53.2 PSF IS REQUIRED. |
| FBC 107.2.1 |
| |
| 10) THE PLANS SPECIFY SINGLE HUNG WINDOWS AND THE |
| PRODUCT APPROVAL SUBMITTED IS FOR DOUBLE HUNG WINDOWS. |
| PLEASE CLARIFY. |
| |
| |