Plan Review Notes For Permit 14070321 |
Permit Number |
14070321 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-08-13 08:10:23 | 2010 FBC | | | | DENIED BY PLUMBING | | | | 1) THE FULL BATH ON THE SECOND FLOOR IS NOT PROPERLY | | VENTED. FBCR P3108.2.1 HORIZONTAL WET VENT. NOT MORE | | THAN ONE WET- VENTED FIXTURE DRAIN SHALL DISCHARGE | | UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION. | | THE TUB DRAIN NEEDS TO DISCHARGE DOWNSTREAM OF THE | | LAVATORY DRAIN CONNECTION. | | | | 2) THE FIRST AND SECOND FLOOR BATHROOM LAVATORIES ARE | | INCORRECTLY LABELED AS SINKS. IT IS IMPORTANT TO USE | | THE PROPER NOMENCLATURE BECAUSE THERE IS A DIFFERENCE | | IN THE REQUIRED TRAP SIZES. PLEASE CORRECT. CITY | | AMENDMENTS 107.2.1 AND FBCR P3201.7 | | | | 3) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | THE PLUMBING DESIGN IS REQUIRED ON THE PLANS. CITY | | AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|