2014-08-13 09:01:32 | 2010 FBC |
| |
| DENIED BY MECHANICAL |
| |
| 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED |
| BY FBC ENERGY CONSERVATION SECTION 103.2.1.1 THE |
| PREPARER AND THE OWNER/AGENT IS REQUIRED TO SIGN THE |
| FORMS. |
| |
| 2) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT |
| SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3. |
| |
| 3) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| THE MECHANICAL DESIGN IS REQUIRED ON THE PLANS. CITY |
| AMENDMENTS 107.2.1 |
| |
| 4) PROVIDE AN EQUIPMENT SCHEDULE FOR THE HEATING AND |
| COOLING EQUIPMENT ON THE MECHANICAL PLANS THAT IS |
| CONSISTENT WITH THE EQUIPMENT SIZING CALCULATIONS. |
| PROVIDE THE MODEL NUMBERS FOR THE AIR HANDLER AND |
| CONDENSING UNIT. CITY AMENDMENTS 107.2.1.3 AND |
| 107.3.5.3 |
| |
| 5) SHOW THE RETURN AIR DUCTWORK FROM THE FIRST FLOOR |
| OFFICE TO THE A/H LOCATED ON THE SECOND FLOOR. SPECIFY |
| THE GRILL SIZE AND DUCT SIZE. CITY AMENDMENTS 107.3.5.3 |
| AND FBCR M1602 |
| |
| 6) SPECIFY THE SIZE OF THE SUPPLY DUCT TO THE HALF BATH |
| ON THE FIRST FLOOR. CITY AMENDMENTS 107.3.5.3 |
| |
| 7) IF THE A/H IS TO BE LOCATED IN A CLOSET, SHOW HOW |
| THE RETURN AIR WILL GET TO THE A/H. SPECIFY RETURN |
| GRILL SIZE. DUCT SIZES, LOUVERED DOOR, ETC. CITY |
| AMENDMENTS 107.3.5.3 AND FBCR M1602 |
| |
| 8) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |