Plan Review Notes
Plan Review Notes For Permit 14070321
Permit Number 14070321
Review Stop M
Sequence Number 1
Notes
Date Text
2014-08-13 09:01:322010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC ENERGY CONSERVATION SECTION 103.2.1.1 THE
 PREPARER AND THE OWNER/AGENT IS REQUIRED TO SIGN THE
 FORMS.
  
 2) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS AS REQUIRED BY FBCR M1401.3.
  
 3) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE MECHANICAL DESIGN IS REQUIRED ON THE PLANS. CITY
 AMENDMENTS 107.2.1
  
 4) PROVIDE AN EQUIPMENT SCHEDULE FOR THE HEATING AND
 COOLING EQUIPMENT ON THE MECHANICAL PLANS THAT IS
 CONSISTENT WITH THE EQUIPMENT SIZING CALCULATIONS.
 PROVIDE THE MODEL NUMBERS FOR THE AIR HANDLER AND
 CONDENSING UNIT. CITY AMENDMENTS 107.2.1.3 AND
 107.3.5.3
  
 5) SHOW THE RETURN AIR DUCTWORK FROM THE FIRST FLOOR
 OFFICE TO THE A/H LOCATED ON THE SECOND FLOOR. SPECIFY
 THE GRILL SIZE AND DUCT SIZE. CITY AMENDMENTS 107.3.5.3
 AND FBCR M1602
  
 6) SPECIFY THE SIZE OF THE SUPPLY DUCT TO THE HALF BATH
 ON THE FIRST FLOOR. CITY AMENDMENTS 107.3.5.3
  
 7) IF THE A/H IS TO BE LOCATED IN A CLOSET, SHOW HOW
 THE RETURN AIR WILL GET TO THE A/H. SPECIFY RETURN
 GRILL SIZE. DUCT SIZES, LOUVERED DOOR, ETC. CITY
 AMENDMENTS 107.3.5.3 AND FBCR M1602
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  