Plan Review Notes For Permit 14070321 |
Permit Number |
14070321 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-08-20 09:06:08 | 2010 FBC / 2008 NEC | | | | DENIED BY ELECTRIC | | | | 1) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | THE ELECTRICAL DESIGN IS REQUIRED ON THE PLANS. CITY | | AMENDMENTS 107.2.1 | | | | 2) SHOW COMPLIANCE WITH FBCR 314 FOR SMOKE ALARMS AND | | 315 FOR CARBON MONOXIDE ALARMS. | | | | 3) ALL RECEPTACLE OUTLETS IN THE GARAGE ARE REQUIRED TO | | BE GFCI PROTECTED. THIS INCLUDES THE ONE FOR THE GARAGE | | DOOR OPENER. NEC 210.8 | | | | 4) EXTERIOR RECEPTCAL OUTLETS ARE REQUIRED TO BE | | WEATHER-PROOF. NEC 406.8 (B) | | | | 5) THE WIRING FROM THE SWITCHES CONTROLLING THE | | EXTERIOR SPOT LIGHTS AND SOME OF THE OTHER EXTERIOR | | LIGHTING OUTLETS ARE NOT INDICATED ON THE PLANS. CITY | | AMENDMENTS 107.2.1 | | | | 6) A RECEPTACLE OUTLET IS REQUIRED AT THE FRONT OF THE | | DWELLING. NEC210.52 (E) (1) | | | | 7) AN APPARENT PRINTING ERROR SHOWS A RECEPTACLE OUTLET | | LOCATED ON THE OVERHEAD GARAGE DOOR. PLEASE CALARIFY. | | CITY AMENDMENTS 107.2.1 | | | | 8) UPDATE THE NFPA CODE EDITIONS SPECIFIED IN THE | | ELECTRICAL NOTES TO THE STANDARDS THAT ARE REFERENCED | | IN CHAPTER 43 OF THE 2010 FBCR. | | | | 9) SHOW COMPLIANCE WITH NEC 250.94 FOR INTERSYSTEM | | BONDING. | | | | 10) SHOW COMPLIANCE WITH NEC 210.12 FOR ARC-FAULT | | CIRCUIT-INTERRUPTER PROTECTION. | | | | 11) SHOW COMPLIANCE WITH NEC 406.11 FOR | | TAMPER-RESISTANT RECEPTACLES. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|