Plan Review Notes For Permit 14070287 |
Permit Number |
14070287 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-07-14 12:13:08 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PROVIDE A VERIFIABLE COPY OF THE CONTRACT FOR THIS | | JOB, FBC 109. | | | | 2. PROVIDE A PLAN WHICH PROVIDES ROOM DESIGNATIONS. THE | | CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%. FBC | | 2010 RESIDENTIAL 310, FBC 2010 EXISTING BUILDING 604.1. | | | | | 2014-07-14 12:07:58 | ***PROVISO*** | | ***ISSUED AT CONTRACTOR'S RISK**** | | | | FBC R310, FBC EB 604.1. FOR BEDROOM WINDOWS, THE CLEAR | | OPENING CANNOT BE REDUCED BY MORE THAN 5%. | | | | NO ROOM DESIGNATIONS SHOWN ON THE PLAN | | | | AT INSPECTION, PROVIDE A PLAN WHICH SHOWS ROOM | | DESIGNATIONS. IF ANY OF THE PROPOSED EMERGENCY ESCAPE | | AND RESCUE OPENINGS EXCEED THE 5% REDUCTION OF CLEAR | | OPENING ALLOWED BY THE CODE, SUBMIT A REVISION CHANGING | | TO A COMPLIANT WINDOW | | | | |
|