Plan Review Notes For Permit 14070269 |
Permit Number |
14070269 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-07-10 15:27:29 | ***PROVISO*** | | ***ISSUED AT CONTRACTOR'S RISK**** | | | | AT INSPECTION, PROVIDE A FLOOR PLAN WHICH SHOWS | | LOCATIONS OF SINGLE HUNG AND HORIZONTAL ROLLER WINDOWS. | | | | FBC R310, FBC EB 604.1. FOR SLEEPING ROOM WINDOWS, THE | | CLEAR EMERGENCY ESCAPE AND RESCUE OPENING CANNOT BE | | REDUCED BY MORE THAN 5%. | | | | 38" HIGH BEDROOM WINDOWS ARE SHOWN ON THE FLOOR PLAN. | | HORIZONTAL ROLLER WINDOWS ARE ASSUMED TO BE INSTALLED | | IN THESE LOCATIONS. | | | | IF THE 38" HIGH BEDROOM WINDOWS ARE TO HAVE SINGLE HUNG | | WINDOWS INSTALLED, SUBMIT A REVISION WITH CALCULATIONS | | TO SHOW THAT THE CLEAR OPENING IS NOT REDUCED BY MORE | | THAN 5%. | | | | |
|