Plan Review Notes For Permit 14070211 |
Permit Number |
14070211 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-07-29 13:38:28 | | | PLUMBING PLAN REVIEW | | PERMIT: 14070211 | | ADD: 8100 IBIS BLVD | | CONT: HUGH INDUSTRIES | | TEL: (561)792-8004 | | | | 2010 FLORIDA BUILDING CODE W | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2ND REVIEW | | DATE: 7/29/2014 | | | | ACTION: PLUMBING PROVISO | | | | THIS GREASE INTERCEPTOR HAS BEEN DESIGNED UNDER THE | | 2010 FBC-PLUMBING CODE SECTION 1003.3.4 TOTAL FLOW RATE | | WITH RATE OF FLOW CONTROL (1003.3.4.2) . | | THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR | | ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE | | CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND | | LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF | | 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS | | IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR | | SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT | | TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES | | FAHRENHEIT (65.56 DEGREES CELSIUS). | | | | IF THIS AMOUNT OF FATS, OILS OR GREASE IS EXCEEDED THE | | REQUIRED MAINTENANCE & PUMP-OUT SCHEDULE WILL BE | | INCREASED TO KEEP IN COMPLIANCE WITH THE CITY'S | | MUNICIPAL CODE OF ORDINANCES. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|