Plan Review Notes
Plan Review Notes For Permit 14070211
Permit Number 14070211
Review Stop P
Sequence Number 2
Notes
Date Text
2014-07-29 13:38:28 
 PLUMBING PLAN REVIEW
 PERMIT: 14070211
 ADD: 8100 IBIS BLVD
 CONT: HUGH INDUSTRIES
 TEL: (561)792-8004
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
 2ND REVIEW
 DATE: 7/29/2014
  
 ACTION: PLUMBING PROVISO
  
 THIS GREASE INTERCEPTOR HAS BEEN DESIGNED UNDER THE
 2010 FBC-PLUMBING CODE SECTION 1003.3.4 TOTAL FLOW RATE
 WITH RATE OF FLOW CONTROL (1003.3.4.2) .
 THE CITY FOG INSPECTORS (FATS, OILS & GREASE) MONITOR
 ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE
 CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF
 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS
 IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR
 SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT
 TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES
 FAHRENHEIT (65.56 DEGREES CELSIUS).
  
 IF THIS AMOUNT OF FATS, OILS OR GREASE IS EXCEEDED THE
 REQUIRED MAINTENANCE & PUMP-OUT SCHEDULE WILL BE
 INCREASED TO KEEP IN COMPLIANCE WITH THE CITY'S
 MUNICIPAL CODE OF ORDINANCES.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  