2014-07-15 13:55:54PLUMBING PLAN REVIEW
 PERMIT: 14070211
 ADD: 8100 IBIS BLVD
 CONT: HUGHES CONSTRUCTION INDUSTRIES
 TEL: (561)792-8004
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:JULY 15/ 2014
 ACTION: DENIED
  
 1) PLANS SUBMITTED ARE SITE PLAN SHOWING THE LOCATION
 OF THE PROPOSED (2) GREASE INTERCEPTORS AND SPECS ON A
 SCHIER GREAT BASIN 250 GREASE INTERCEPTOR. THERE WAS NO
 INFORMATION HOW THESE GREASE INTERCEPTORS WERE SIZED.
 2010 FBC-P 1003.2 APPROVAL. THE SIZE, TYPE AND LOCATION
 OF EACH INTERCEPTOR AND OF EACH SEPARATOR SHALL BE
 APPROVED BY THE PLUMBING OFFICIAL. THE INTERCEPTOR OR
 SEPARATOR SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER?S INSTRUCTIONS AND THE
 REQUIREMENTS OF THIS SECTION. WASTES THAT DO NOT
 REQUIRE TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED
 INTO ANY INTERCEPTOR OR SEPARATOR.
  
 2) SHOW COMPLIANCE WITH 003.3.1 GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS.GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED.
  
 3) SHOW HOW THE GREASE INTERCEPTOR WAS SIZED AND IN
 COMPLIANCE WITH:
 2010 FBC-P 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC
 GREASE REMOVAL DEVICES.
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
  
 ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE
 CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND
 LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF
 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS
 IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR
 SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT
 TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES
 FAHRENHEIT (65.56 DEGREES CELSIUS).
  
 IF THIS AMOUNT OF FATS, OILS OR GREASE IS EXCEEDED THE
 REQUIRED MAINTENANCE & CLEANOUT SCHEDULE WILL BE
 INCREASED TO KEEP IN COMPLIANCE WITH THE CITY'S
 MUNICIPAL CODE OF ORDINANCES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
 7/18/2014 JULIAN BLAZER CALLED (THE WEITZ CO
 REPRESENTATIVE) IN REFERANCE TO THIS PERMIT. IN
 REVIEWING THE APPROVED PLANS SHEET PL003 THE GREASE
 TRAP IS SIZED USING THE 2010 FBC-P TABLE 1003.5.1 WHICH
 IS FOR CONCRETE VAULT TYPE INTERCEPTORS. THE SUBMITTED
 PRODUCT IS SCHIER (2) GB-250 TYPE HYDROMECHANICAL
 GREASE INTERCEPRTORS, NOT THE TYPE OF INTERCEPTOR THE
 DESIGNER OF RECORD REQUIRES ,NOR HAS APPROVED WITH
 THEIR SHOP DRAWING STAMP OF APPROVAL.
  
 PLEASE NOTE A REVISION WILL BE NEEDED TO THE PLAN SINCE
 THE FORMULA AND SIZING ON PL003 IS FOR A CONCRETE VAULT
 TYPE INTERCEPTOR. 2ND THE SCHIER GREASE INTERCEPTOR
 WILL NEED TO BE SIZED USING THIER OWN FORMULA FOR
 GREASE REMOVAL & RETENTION, REVIEWED BY THE DESIGNER OF
 RECORD, AND SHOP DRAWING STAMP OF APPROVAL ON THE
 DOCUMENTS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676