2014-08-04 10:08:27 | RE-ROOF BUILDING REVIEW SECOND CHECKLIST. |
| CODE: 2010 FBC. |
| |
| 1- PER MEETING WITH CONTRACTOR ON 7/14/14: |
| |
| EXISTING ROOF DRAINS ARE GOING TO BE REMOVED. NEED TO |
| PROVIDE PLANS SHOWING COMPLIANCE WITH THE ROOF DRAINAGE |
| SEC. 1503.4 OF 2010 FBC-BUILDING. ***NOTE: PERMIT |
| OBTAINED BY THE GENERAL CONTRACTOR TO DO THE DAYCARE |
| RENOVATION DOESN'T INCLUDE REMOVAL OF THE ROOF DRAINS |
| AND DOESN'T INCLUDE THE STRUCTURAL ROOF REPAIRS. NEED |
| TO PROVIDE COMPLETE DRAWINGS AND SPECIFICATIONS UNDER A |
| REVISION TO PERMIT 13100594 (OR APPLY FOR NEW PERMIT) |
| SHOWING THE ROOF DRAINS REMOVAL AND THE SPECIFICATIONS |
| FOR THE STRUCTURAL ROOF REPAIRS. (COMMENT NOT |
| ADDRESSED). |
| |
| 2- TAS 105 REPORT SHOWS AREAS WITH "BAD DECK". PROVIDE |
| COMPLETE DETAILS/ SPECIFICATIONS AS A REVISION TO |
| PERMIT #13100594 OR APPLY FOR NEW PERMIT FOR DECK |
| REPAIRS. SEC. 107.2.1 CITY AMENDMENTS TO FBC. (***NOTE: |
| COORDINATE WITH ITEM #1 ABOVE). CONTRACTOR DOING THE |
| DECK REPAIRS TO HAVE PROPER LICENSE AS REQUIRED BY SEC. |
| 489.113 FLORIDA STATUTES. |
| |
| ******ADDITIONAL COMMENTS TO ENGINEER DETAILS SUBMITTED |
| FOR THE ROOF REPAIRS: |
| (A) ENGINEER TO PROVIDE NAME AND LICENSE NUMBER AS |
| REQUIRED BY CHAPTER 471 FLORIDA STATUTES. |
| |
| (B) ENGINEER TO COORDINATE ROOF DECK MATERIALS WITH THE |
| PRODUCT APPROVAL AND FIELD WITHDRAWAL RESISTANCE TEST |
| (TAS 105) SUBMITTED. IS IT LIGHT WEIGHT CONCRETE DECK |
| OR GYPSUM DECK?. REVISE AS REQUIRED TO MATCH. SEC. |
| 107.2.1 CITY AMENDMENTS TO FBC. |
| |
| |
| 3- ROOF NEEDS POSITIVE DRAINAGE AS REQUIRED BY |
| EXCEPTION ON SEC. 611.1 OF 2010 FBC-EXISTING BUILDING |
| CODE. (COMMENT NOT ADDRESSED. COORDINATE WITH ITEM #1 |
| ABOVE). |
| |
| |