2014-07-05 11:59:09 | BUILDING PLAN REVIEW |
| PERMIT: 14070081 |
| ADD: 316 ELLAMAR RD. |
| CONT: VERSATILE BUILDERS |
| TEL: (561)845-9421 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: JULY 05/2014 |
| ACTION: DENIED |
| |
| 1) . SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| FBC-2010 FUEL GAS. |
| |
| 2). BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. |
| 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) |
| THE TABLE SUBMITTED IS NOT A CURRENT TABLE FROM EITHER |
| THE 2010 FLORIDA RESIDENTUAL OR BUILDING - FUEL-GAS |
| CODES. |
| |
| 3). SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? |
| USE OF CAPACITY SECTION A.3.1(4) |
| |
| 4). SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2010 FUEL GAS SEC. 402.2 THE SUBMITTED CUR SHEET |
| LIST RHEEM, PALOMA/ WAI WELA, RUUD, RICHMOND AS |
| PRODUCTS ALL COVERED UNDER THIS SPEC SHEET, WHICH |
| MANUFACTURER IS IT. |
| |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |