2014-07-05 11:59:09BUILDING PLAN REVIEW
 PERMIT: 14070081
 ADD: 316 ELLAMAR RD.
 CONT: VERSATILE BUILDERS
 TEL: (561)845-9421
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 05/2014
 ACTION: DENIED
  
 1) . SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2010 FUEL GAS.
  
 2). BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS.
 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
 THE TABLE SUBMITTED IS NOT A CURRENT TABLE FROM EITHER
 THE 2010 FLORIDA RESIDENTUAL OR BUILDING - FUEL-GAS
 CODES.
  
 3). SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 4). SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2 THE SUBMITTED CUR SHEET
 LIST RHEEM, PALOMA/ WAI WELA, RUUD, RICHMOND AS
 PRODUCTS ALL COVERED UNDER THIS SPEC SHEET, WHICH
 MANUFACTURER IS IT.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  