2014-07-15 10:26:08 | PLUMBING PLAN REVIEW |
| PERMIT: 14070049 |
| ADD: 223 CLEMATIS ST |
| CONT: PAUL DAVIS CONSTRUCTION |
| TEL: (561)848-0577 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: MON. JULY 14/2014 |
| ACTION: PLUMBING PROVISO |
| |
| THIS GREASE INTERCEPTOR HAS BEEN DESIGNED UNDER THE |
| 2010 FBC-PLUMBING CODE SECTION 1003.3.4 TOTAL FLOW RATE |
| WITH RATE OF FLOW CONTROL |
| (1003.3.4.2). THE CITY FOG INSPECTORS (FATS, OILS & |
| GREASE) MONITOR ALL GREASE INTERCEPTORS TO VERIFY |
| COMPLIANCE WITH THE CITY'S MUNI CODE |
| SEC. 90-126. PROHIBITIONS AND LIMITATIONS OF |
| DISCHARGE.(7) MINERAL OIL IN EXCESS OF 50 MG/L OR |
| ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS IN EXCESS |
| OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR SUBSTANCES |
| WHICH MAY SOLIDIFY OR BECOME VISCOUS AT TEMPERATURES |
| LOWER THAN OR EQUAL TO 150 DEGREES FAHRENHEIT (65.56 |
| DEGREES CELSIUS). |
| IF THIS AMOUNT OF FATS, OILS OR GREASE IS EXCEEDED THE |
| REQUIRED MAINTENANCE & CLEANOUT SCHEDULE WILL BE |
| INCREASED TO KEEP IN COMPLIANCE WITH THE CITY'S |
| MUNICIPLE CODE OF ORDINANCES. |
| |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |