Plan Review Notes For Permit 14070043 |
Permit Number |
14070043 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-07-10 10:43:08 | DATE: 7/9/2014 | | PROJECT: ROSEN RESIDENCE. | | PERMIT#: 14070043 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL | | 314.3.1 | | | | 2) PROVIDE PRODUCT APPROVALS AND INSTALLATION DETAILS | | FOR MOTORIZED SHADES, RIBBON LIGHTING, PENDENT | | FIXTUURES AND RECESSED LIGHTING. LISTING AND LABELING | | REQUIRED BY AN APPROVED TESTING LAB. IN JUDGING | | EQUIPMENT, CONSIDERATION SUCH AS THE FOLLOWING SHALL BE | | EVALUATED: SUITABILITY FOR INSTALLATION AND USE IN | | CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC | | 110.3(A)(1 THRU 8) | | | | 3) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN | | ACCORDANCE WITH THE PROVISIONS OF NEC 410.16(A) AND | | (B). REVISE PLANS TO INDICATE COMPLIANCE. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|