2014-07-03 13:28:40DATE: 7/3/2014
 PROJECT: RONICA HARWAY
 PERMIT#: 14070037
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE THE LOCATION OF THE MAIN SERVICE ON THE
 FLOOR/SITE PLAN. INDICATE THE CIRCUITING ON THE FLOOR
 PLAN IN RELATION TO THE PANEL SCHEDULE. FBC 107.2.1
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. FBC 107.2.1
  
 2) INDICATE ON THE PLANS ALL REQUIRED OUTLETS PER
 210.52.
 GUEST ROOMS OR GUEST SUITES IN HOTELS, MOTELS, SLEEPING
 ROOMS IN DORMITORIES AND SIMILAR OCCUPANCIES SHALL HAVE
 RECEPTACLES INSTALLED IN ACCORDANCE WITH 210.52(A) AND
 210.52(D). GUEST ROOMS OR GUEST SUITES PROVIDED WITH
 PERMANENT PROVISIONS FOR COOKING SHALL HAVE RECEPTACLE
 OUTLETS INSTALLED IN ACCORDANCE WITH ALL OF THE
 APPLICABLE RULES IN 210.52. NEC 210.60(A) GENERAL
  
 3) INDICATE ON THE PLAN THE NEW CEILING FANS WILL BE
 SUPPORTED ACCORDINGLY. NEC 314.27(B)
 OUTLET BOXES OR FITTINGS DESIGNED FOR THE SUPPORT OF
 LUMINAIRES AND INSTALLED AS REQUIRED BY 314.233 SHALL
 BE PERMITTED TO SUPPORT A LUMINAIRE WEIGHING 50LBS OR
 LESS. A LUMINAIRE THAT WEIGHS MORE THAN 50LBS SHALL BE
 SUPPORTED INDEPENDENTLY OF THE OUTLET BOX UNLESS THE
 OUTLET BOX IS LISTED AND MARKED FOR THE MAXIMUM WEIGHT
 TO BE SUPPORTED. NEC 314.27(B).
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]