2014-07-10 07:17:081ST REVIEW: 2010 FBC
  
 THE APPLICANT HAS USED THE DESIGN GUIDE BELOW.
  
 FBC-R301.2.1.1.1 DESIGN.
 THE FOLLOWING DESIGN GUIDE SHALL BE ACCEPTED AS
 CONFORMING TO ACCEPTED ENGINEERING PRACTICES: AAF GUIDE
 TO ALUMINUM CONSTRUCTION IN HIGH-WIND AREAS. VINYL AND
 ACRYLIC PANELS SHALL BE REMOVABLE. REMOVABLE PANELS
 SHALL BE IDENTIFIED AS REMOVABLE BY A DECAL. THE
 IDENTIFICATION DECAL SHALL ESSENTIALLY STATE:
 ?REMOVABLE PANEL SHALL BE REMOVED WHEN WIND SPEEDS
 EXCEED 75 MPH (34 M/S).? DECALS SHALL BE PLACED SUCH
 THAT THE DECAL IS VISIBLE WHEN THE PANEL IS INSTALLED.
  
 PLEASE EXPLAIN HOW YOU CAN HAVE TWO SHEETS FROM THE
 REFERENCED MANUAL WITH IDENTICAL PAGE NUMBERS AND
 EDITIONS, BUT DIFFERENT DETAILS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  