Plan Review Notes For Permit 14070012 |
Permit Number |
14070012 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-08-11 17:08:53 | APPROVED WITH EXCEPTIONS. | | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS FOR | | THE THE NEW A/C UNITS AS REQUIRED BY FBCR M1401.3. | | 2) SUBMIT AHRI CERTIFICATIONS FOR THE NEW HEATING AND | | COOLING EQUIPMENT. FBC ENERGY CONSERVATION SECTION | | 402.1.2.4. | | 3) REVISE THE SIZE OF THE THROUGH THE WALL TRANSFER | | GRILL AT THE GUEST BEDROOM TO COMPLY WITH FBCR M1602.4 | | FOR BALANCED RETURN AIR. | | TRANSFER GRILLS SHALL USE 50 SQUARE INCHES OF GRILL | | AREA TO 100 CFMS OF SUPPLY AIR. | | 4) PROVIDE TWO SETS OF AN EQUIPMENT ANCHORING DETAIL | | FOR THE MECHANICAL EQUIPMENT THAT IS EXPOSED TO WIND | | LOADS. FBCR M1307.2.1 | | | | |
|