Plan Review Notes
Plan Review Notes For Permit 14070012
Permit Number 14070012
Review Stop M
Sequence Number 2
Notes
Date Text
2014-08-11 17:08:53APPROVED WITH EXCEPTIONS.
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS FOR
 THE THE NEW A/C UNITS AS REQUIRED BY FBCR M1401.3.
 2) SUBMIT AHRI CERTIFICATIONS FOR THE NEW HEATING AND
 COOLING EQUIPMENT. FBC ENERGY CONSERVATION SECTION
 402.1.2.4.
 3) REVISE THE SIZE OF THE THROUGH THE WALL TRANSFER
 GRILL AT THE GUEST BEDROOM TO COMPLY WITH FBCR M1602.4
 FOR BALANCED RETURN AIR.
 TRANSFER GRILLS SHALL USE 50 SQUARE INCHES OF GRILL
 AREA TO 100 CFMS OF SUPPLY AIR.
 4) PROVIDE TWO SETS OF AN EQUIPMENT ANCHORING DETAIL
 FOR THE MECHANICAL EQUIPMENT THAT IS EXPOSED TO WIND
 LOADS. FBCR M1307.2.1
  
  