2014-07-25 09:15:02DATE: 7/25/2014
 PROJECT: 224 LAKEWOOD RD.
 PERMIT#: 14070012
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THERE IS AN ELECTRICAL PERMIT APPLICATION INCLUDED
 WITH THIS SUBMITTAL PACKAGE HOWEVER THERE ARE NO
 ELECTRICAL PLANS OR SPECIFICATIONS INCLUDED AS REQUIRED
 FOR REVIEW. PROVIDE COMPLETE PLANS AND SPECIFICATIONS
 TO INCLUDE THE FOLLOWING: FBC WPB AMENDMENTS, SECTION
 107.2.1
 1. A DETAILED SCOPE OF ELECTRICAL WORK TO BE PERFORMED.
 2. A FLOOR PLAN INDICATING THE LOCATION OF THE
 ELECTRICAL PANEL AND ALL THE ITEMS AS IDENTIFIED ON THE
 SCOPE OF WORK.
 3. A ONE LINE RISER DIAGRAM OF THE ELECTRICAL SERVICE
 IF ONE IS TO BE INCLUDED.
 4. A COMPLETE LOAD SUMMARY CALCULATION INDICATING THE
 EXISTING AND NEW LOADS.
 5. A PANEL SCHEDULE WITH A COMPLETE DIRECTORY OF
 CIRCUITRY AS IDENTIFIED ON THE FLOOR PLAN. A
 6. A FIXTURE SCHEDULE INDICATING THE LIGHTING FIXTURES
 PROPOSED INDICATING LOCATIONS LAMP TYPE, LOAD AND
 VOLTAGE.
 7. A SITE PLAN INDICATING THE LOCATION OF THE
 ELECTRICAL SERVICE.
 8. CUT SHEETS OF ANY SPECIALZED EQUIPMENT PROPOSED SUCH
 AS STEAM GENERATORS, TRANSFER SWITCHES GENERATORS, HOME
 AUTOMATION EQUIPMENT, STRUCTURED CABLING CABINETS
 ETC...
 9. REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NOTE: ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 NEC 210.11 (C)
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
 THESE ARE JUST TO NAME A FEW. PLEASE FAMILILIARIZE
 YOURSELF WITH THE 2008 EDITION OF THE NEC AND THE 2010
 EDITION OF THE FBC AND THE WPB AMEMNDMENTS TO CHAPTER
 ONE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  