2014-07-24 09:15:22 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- ARCHITECT TO REVISE DESIGN CRITERIA ON SHEET A-10: |
| A) CLARIFY WHY THE WIND NET UPLIFT IS ONLY FOR ZONES 1 |
| AND 2?. NEED WIND LOADS FOR ALL ZONES. SEC. R301 OF |
| 2010 FBC-RESIDENTIAL. |
| B) REVISE THE BASIC WIND VELOCITY. SPECIFY THE ULTIMATE |
| WIND LOAD AND THE NOMINAL WIND LOAD AS REQUIRED BY SEC. |
| R301.2.1.3 OF 2010 FBC-RESIDENTIAL. (NOTE: ULTIMATE |
| WIND SPEED FOR CITY OF WEST PALM BEACH IS 170MPH). |
| C) REVISE OCCUPANCY. THIS IS NOT 1. THIS IS A SINGLE |
| FAMILY RESIDENCE (R3). |
| |
| 2- ARCHITECT TO REVISE ALL THE WINDOWS AND DOORS DESIGN |
| PRESSURES SHOWN ON THE EXTERIOR ELEVATIONS. THEY DO NOT |
| CORRESPOND TO EXPOSURE "C" ACCORDING TO HEIGHT AND |
| OPENING LOCATION (INTERIOR OR END LOCATION). OR PROVIDE |
| COMPLETE CALCULATIONS SHOWING HOW THE DESIGN PRESSURES |
| SHOWN WERE CALCULATED. SEC. R301.2.1 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) ROOF COVER. NONE SUBMITTED. GENERAL NOTES ON COVER |
| SHEET INDICATES NEW ROOF AS PART OF THE SCOPE OF WORK. |
| ***NOTE: A ROOFING SUB-PERMIT IS REQUIRED ALSO. |
| B) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| ON PLANS, DETAILS AND SPECIFICATIONS. |
| C) WINDOW MULLIONS. NOA 11-0922.01 SUBMITTED WAS |
| SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE |
| DOWNLOAD CURRENT NOA AND RE-SUBMIT. PROVIDE 2 COPIES |
| ONLY ONE SUBMITTED. |
| D) FRENCH DOORS NOA 11-1013.24. ONLY ONE COPY |
| SUBMITTED. PROVIDE ANOTHER COPY. |
| E) CASEMENT WINDOWS NOA 11-1006.05. ONLY ONE COPY |
| SUBMITTED. PROVIDE ANOTHER COPY. |
| F) FIXED WINDOWS NOA 11-1021.17. ONLY ONE COPY |
| SUBMITTED. PROVIDE ANOTHER COPY. |
| G) ROUND CASEMENT WINDOW AS SHOWN ON ELEVATIOINS. |
| |
| 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| |
| 5- ARCHITECT TO REVISE WINDOW AND DOOR SCHEDULES TO |
| MATCH PRODUCT APPROVALS SUBMITTED. FOR EXAMPLE FRENCH |
| DOORS PRODUCT APPROVAL SUBMITTED IS FOR ALUMINUM DOORS |
| NOT WOOD. REVISE AS REQUIRED TO MATCH. SEC. 103.2.2 OF |
| 2010 FBC-ENERGY CONSERVATION. |
| |
| 6- SHEET A-2: |
| A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| INTERIOR HANDRAIL TO BE REPLACED TO VERIFY COMPLIANCE |
| WITH TABLE R301.5 AND SEC. R311.7.7 OF 2010 |
| FBC-RESIDENTIAL. |
| B) POWDER ROOM #105. EXISTING WINDOW IS GOING TO BE |
| BLOCKED. PROVIDE SPECIFICATIONS FOR VENTILATION. SEC. |
| R303.3 OF 2010 FBC-RESIDENTIAL. |
| |
| 7- A) WINDOW SCHEDULE ON SHEET A-5 IS MISSING WINDOW |
| "N". PROVIDE INFORMATION FOR WINDOW "N" TO VERIFY |
| COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. 604.1 |
| OF 2010 FBC-EXISTING BUILDING. |
| B) CLARIFY WINDOW "B". IS IT A CASEMENT OR FIXED |
| WINDOW?. IS IT ROUND OR SQUARE TOP?. EXTERIOR ELEVATION |
| SHOWS ROUND TOP. CLARIFY AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS TO FBC. |
| |
| 8- SHEET A-4: PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS FOR NEW MASTER BATHROOM BALCONY TO |
| VERIFY COMPLIANCE WITH TABLE R301.5 AND SEC. R312 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| 9- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR NEW ARCHED OPENINGS IN THE REBUILT DEN AREA ON |
| FIRST FLOOR. SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| |
| 10- SHEET A-9: REVISE ALL THE DOOR STRUCTURAL BUCK |
| DETAILS. BUCK NEED TO PROVIDE FULL SUPPORT TO THE DOOR |
| FRAME AS REQUIRED BY SEC. R612.10.2.1 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |