2014-07-02 18:17:052010 FBC
  
 REVISION IS DENIED
  
 1) BECAUSE THE REVISED PAGE IS NOT REPLACING SHEET S.01
 OF THE APPROVED STRUCTURAL PLANS, IT SHOULD NOT BE
 NUMBERED AS S-1. PLEASE USE A NUMBER FOR THE REVISED
 PLAN THAT WILL NOT BE CONFUSED WITH SHEETS S.01 OR S.02
 OF THE APPROVED PLANS. CITY AMENDMENTS 107.2.1.4 AND FS
 471
  
 2) THE DESIGNER OF RECORD FOR THIS PROJECT IS A FLORIDA
 LICENSED ARCHITECT, STEPHEN MICHAEL ROY. THE REVISED
 PLANS ARE SIGNED AND SEALED BY A FLORIDA LICENSED
 ENGINEER, JOHN HOLT. THERE IS NO STRUCTURAL OR
 CONSULTING ENGINEER SPECIFIED ON THE APPROVED PLANS. IN
 ORDER FOR THE REVISED PLANS TO BE ACCEPTED, THE
 DESIGNER OF RECORD WILL HAVE TO SUBMIT A LETTER STATING
 THAT THE ENGINEER IS RESPONSIBLE FOR THE STRUCTURAL
 WORK SHOWN ON HIS NEW PLANS OR THE REVISED PLANS WILL
 NEED TO BE STAMPED WITH THE ARCHITECT'S SHOP DRAWING
 REVIEW STAMP AND MARKED AS ACCEPTED. FS 471 AND 481
  
 3) THE EXPOSURE CATEGORY ON THE REVISED STRUCTURAL
 DRAWING IS INCORRECT. THE STRUCTURE IS LOCATED IN
 EXPOSURE CATEGORY 'D' . PLEASE CORRECT. FBCR
 301.2.1.4.3
  
 4) DETAIL B ON S-1, SPECIFIES (2) 5/8" DIA. X 12" LONG
 THRU BOLTS TO THE MASONRY WALL WITH 8 " EMBED, BUT DOES
 NOT SPECIFY THE EPOXY THAT WILL BE USED TO ANCHOR IT
 AND THE DRAWING DOES NOT SHOW THE BOLT EXTENDING INTO
 THE FILLED CONCRETE BLOCK CELL. PLEASE CORRECT CITY
 AMENDMENTS 107.2.1 AND FBCR 301.1
  