2014-07-02 18:17:05 | 2010 FBC |
| |
| REVISION IS DENIED |
| |
| 1) BECAUSE THE REVISED PAGE IS NOT REPLACING SHEET S.01 |
| OF THE APPROVED STRUCTURAL PLANS, IT SHOULD NOT BE |
| NUMBERED AS S-1. PLEASE USE A NUMBER FOR THE REVISED |
| PLAN THAT WILL NOT BE CONFUSED WITH SHEETS S.01 OR S.02 |
| OF THE APPROVED PLANS. CITY AMENDMENTS 107.2.1.4 AND FS |
| 471 |
| |
| 2) THE DESIGNER OF RECORD FOR THIS PROJECT IS A FLORIDA |
| LICENSED ARCHITECT, STEPHEN MICHAEL ROY. THE REVISED |
| PLANS ARE SIGNED AND SEALED BY A FLORIDA LICENSED |
| ENGINEER, JOHN HOLT. THERE IS NO STRUCTURAL OR |
| CONSULTING ENGINEER SPECIFIED ON THE APPROVED PLANS. IN |
| ORDER FOR THE REVISED PLANS TO BE ACCEPTED, THE |
| DESIGNER OF RECORD WILL HAVE TO SUBMIT A LETTER STATING |
| THAT THE ENGINEER IS RESPONSIBLE FOR THE STRUCTURAL |
| WORK SHOWN ON HIS NEW PLANS OR THE REVISED PLANS WILL |
| NEED TO BE STAMPED WITH THE ARCHITECT'S SHOP DRAWING |
| REVIEW STAMP AND MARKED AS ACCEPTED. FS 471 AND 481 |
| |
| 3) THE EXPOSURE CATEGORY ON THE REVISED STRUCTURAL |
| DRAWING IS INCORRECT. THE STRUCTURE IS LOCATED IN |
| EXPOSURE CATEGORY 'D' . PLEASE CORRECT. FBCR |
| 301.2.1.4.3 |
| |
| 4) DETAIL B ON S-1, SPECIFIES (2) 5/8" DIA. X 12" LONG |
| THRU BOLTS TO THE MASONRY WALL WITH 8 " EMBED, BUT DOES |
| NOT SPECIFY THE EPOXY THAT WILL BE USED TO ANCHOR IT |
| AND THE DRAWING DOES NOT SHOW THE BOLT EXTENDING INTO |
| THE FILLED CONCRETE BLOCK CELL. PLEASE CORRECT CITY |
| AMENDMENTS 107.2.1 AND FBCR 301.1 |
| |