Notes
Date Text
2015-07-09 13:40:50APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 NFPA 72.SECTION 29.8.3.4 SPECIFIC SMOKE DETECTOR
 LOCATION REQUIREMENTS:
 THE INSTALLATION OF SMOKE ALARMS AND SMOKE DETECTORS
 SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS:
 (1) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 LOCATED WHERE AMBIENT CONDITIONS, INCLUDING HUMIDITY
 AND TEMPERATURE, ARE OUTSIDE THE LIMITS SPECIFIED BY
 THE MANUFACTURER?S PUBLISHED INSTRUCTIONS.
 (2) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 LOCATED WITHIN UNFINISHED ATTICS OR GARAGES OR IN OTHER
 SPACES WHERE TEMPERATURES CAN FALL BELOW 40?F (4?C) OR
 EXCEED 100?F (38?C).
 (3)*WHERE THE MOUNTING SURFACE COULD BECOME
 CONSIDERABLY WARMER OR COOLER THAN THE ROOM, SUCH AS A
 POORLY INSULATED CEILING BELOW AN UNFINISHED ATTIC OR
 AN EXTERIOR WALL, SMOKE ALARMS AND SMOKE DETECTORS
 SHALL BE MOUNTED ON AN INSIDE WALL.
 (4)*SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN AN AREA OF EXCLUSION DETERMINED BY A
 10 FT (3.0 M) RADIAL DISTANCE ALONG A HORIZONTAL FLOW
 PATH FROM A STATIONARY OR FIXED COOKING APPLIANCE,
 UNLESS LISTED FOR INSTALLATION IN CLOSE PROXIMITY TO
 COOKING APPLIANCES. SMOKE ALARMS AND SMOKE DETECTORS
 INSTALLED BETWEEN 10 FT (3.0 M) AND 20 FT (6.1 M) ALONG
 A HORIZONTAL FLOW PATH FROM A STATIONARY OR FIXED
 COOKING APPLIANCE SHALL BE EQUIPPED WITH AN
 ALARM-SILENCING MEANS OR USE PHOTOELECTRIC DETECTION.
 EXCEPTION: SMOKE ALARMS OR SMOKE DETECTORS THAT USE
 PHOTOELECTRIC DETECTION SHALL BE PERMITTED FOR
 INSTALLATION AT A RADIAL DISTANCE GREATER THAN 6 FT
 (1.8 M) FROM ANY STATIONARY OR FIXED COOKING APPLIANCE
 WHEN THE FOLLOWING CONDITIONS ARE MET:
 (A) THE KITCHEN OR COOKING AREA AND ADJACENT SPACES
 HAVE NO CLEAR INTERIOR PARTITIONS OR HEADERS AND
 (B) THE 10 FT (3.0 M) AREA OF EXCLUSION WOULD PROHIBIT
 THE PLACEMENT OF A SMOKE ALARM OR SMOKE DETECTOR
 REQUIRED BY OTHER SECTIONS OF THIS CODE.
 (5)*SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM
 A DOOR TO A BATHROOM CONTAINING A SHOWER OR TUB.
 (6) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM
 THE SUPPLY REGISTERS OF A FORCED AIR HEATING OR COOLING
 SYSTEM AND SHALL BE INSTALLED OUTSIDE OF THE DIRECT
 AIRFLOW FROM THOSE REGISTERS.
 (7) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM
 THE TIP OF THE BLADE OF A CEILING-SUSPENDED (PADDLE)
 FAN.
 (8) WHERE STAIRS LEAD TO OTHER OCCUPIED LEVELS, A SMOKE
 ALARM OR SMOKE DETECTOR SHALL BE LOCATED SO THAT SMOKE
 RISING IN THE STAIRWAY CANNOT BE PREVENTED FROM
 REACHING THE SMOKE ALARM OR SMOKE DETECTOR BY AN
 INTERVENING DOOR OR OBSTRUCTION.
 (9) FOR STAIRWAYS LEADING UP FROM A BASEMENT, SMOKE
 ALARMS OR SMOKE DETECTORS SHALL BE LOCATED ON THE
 BASEMENT CEILING NEAR THE ENTRY TO THE STAIRS.
 (10)*FOR TRAY-SHAPED CEILINGS (COFFERED CEILINGS),
 SMOKE ALARMS AND SMOKE DETECTORS SHALL BE INSTALLED ON
 THE HIGHEST PORTION OF THE CEILING OR ON THE SLOPED
 PORTION OF THE CEILING WITHIN 12 IN. (300 MM)
 VERTICALLY DOWN FROM THE HIGHEST POINT.
 (11) SMOKE ALARMS AND DETECTORS INSTALLED IN ROOMS WITH
 JOISTS OR BEAMS SHALL COMPLY WITH THE REQUIREMENTS OF
 17.7.3.2.4.
 (12) HEAT ALARMS AND DETECTORS INSTALLED IN ROOMS WITH
 JOISTS OR BEAMS SHALL COMPLY WITH THE REQUIREMENTS OF
 17.6.3.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
2015-07-06 15:26:30NEW DRAWINGS SUBMITTED. JG.