Plan Review Notes For Permit 14061326 |
Permit Number |
14061326 |
|
Review Stop |
B |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2015-08-14 14:54:11 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- REVISE "METAL HANDRAIL DETAIL ON SHEET A-2 TO MATCH | | FLOOR PLAN AND FRONT ELEVATION. IS THERE A HANDRAIL AND | | GUARDRAIL?. REVISE SIZE OF METAL FRAMING MEMBERS 1-1/2 | | AND 2"?. SPECIFY CONNECTIONS TO CONCRETE STEP AND TO | | COLUMN. | | 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | CONSTRUCTION OF STEPS AND SPECIFY RISER AND TREAD TO | | SHOW COMPLIANCE WITH SEC. R311.7.4. | | 3- REVISE WALL SECTION A/A-2: SCREEN VENTS AT 24" O.C. | | DON'T PROVIDE CROSS VENTILATION. | | 4- SHEET A2: | | A) REVISE PORCH SECTION: (1) SPECIFICATIONS CALL FOR | | (3)2X10 WD BEAM. ONLY 2 ARE SHOWN. | | (2) ROOF RAFTERS ARE 2X6. ROOF FRAMING CALLS FOR 2X8. |
|