2015-04-13 17:26:48 | RESIDENTIAL (R3) ALTERATION/ ADDITION FOURTH BUILDING |
| REVIEW CHECKLIST. |
| CODE: 2010 FBC. |
| |
| NOTE: THESE COMMENTS APPLY TO FRONT AND REAR BUILDINGS. |
| DRAWINGS A-1 TO A-5 SUBMITTED: |
| |
| 1- SITE PLAN SHOWN ON SHEET A-1 DOESN'T MATCH SITE PLAN |
| SHOWN ON SHEET A-5. AND IS MISSING THE CONNECTION |
| (LAUNDRY ROOM) OF THE GARAGE WITH THE REAR BUILDING. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 2- SCOPE OF WORK SPECIFIED ON SHEET A-1 DOESN'T MATCH |
| SCOPE OF WORK SPECIFIED ON SHEET A-5. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 3- DESIGN DATA FOR WIND LOADS SHOWN ON SHEET A-1 |
| DOESN'T MATCH DESIGN DATA SPECIFIED ON SHEET A-5. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 4- INFORMATION SHOWN ON THE DESIGN DATA ON SHEET A-1 |
| AND SHEET A-5 IS CONFUSING. INFORMATION FOR INTERIOR |
| AND END ZONE IS REPEATED TWICE BUT THE DESIGN PRESSURES |
| ARE DIFFERENT. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| PROFESSIONAL FEES FEES. PROVIDE COPY OF SIGNED CONTRACT |
| THAT DESCRIBES ALL THE SCOPE OF WORK. SEC. 109.3 CITY |
| AMENDMENTS. |
| |
| 6- SHEET A-1: |
| A) PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR THE INSTALLATION OF THE NEW ATTIC ACCESS WITH |
| LADDER. |
| |
| B) ENGINEER OF RECORD TO SPECIFY THE ALTERATION LEVEL |
| TYPE OR COMBINATION OF LEVELS OF ALTERATION AS REQUIRED |
| BY SEC. 401.4 OF 2010 FBC-EXISTING BUILDING. |
| |
| C) CLEARLY SPECIFY WHICH WINDOWS AND EXTERIOR DOORS ARE |
| EXISTING AND WHICH ARE GOING TO BE REPLACED. IF |
| REPLACING EXISTING BEDROOM WINDOWS, THEN SPECIFY |
| EXISTING TYPE AND SIZE AND PROPOSED TYPE AND SIZE TO |
| VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. |
| 604 OF 2010 FBC-EXISTING BUILDING. |
| |
| 7- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| |
| 8- COORDINATE LABELING NUMBERS OF BUILDINGS SHOWN ON |
| THE SITE PLAN WITH LABELING OF BUILDINGS SHOWN ON |
| SHEETS A-2 TO A-5. REVISE AS REQUIRED. CLEARLY MATCH |
| BUILDING #1, BUILDING #2 AND BUILDING #3 WITH NUMBERS |
| SHOWN ON THE SITE PLAN. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 9- SHEET A-2: |
| A) PROVIDE GARAGE DOOR COMPLETE FRAMING DETAILS AND |
| SPECIFICATIONS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| |
| B) PROVIDE STAIRS, HANDRAILS AND GUARDRAIL THAT MATCHES |
| NEW PORCH ON SHEET A-5. PROVIDE COMPLETE FRAMING |
| DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE |
| LIVE LOADS OF TABLE R301.5 OF 2010 FBC-RESIDENTIAL. |
| SPECIFY ALL FRAMING MEMBERS AND FASTENERS. |
| |
| C) INFORMATION SHOWN ON THE WOOD FRAMING DETAIL |
| SECTION, WALL SECTION AND DOOR FRAMING SECTION DOESN'T |
| MATCH. REVISE AS REQUIRED TO MATCH AND CLARIFY WHERE |
| ARE THESE SECTIONS TAKEN AT. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 10- SHEET A-3: |
| A) WALL SECTION A/A-1: PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING HOW PROVIDING "CROSS VENTILATION |
| IN BLOCKING" AS SPECIFIED ON THE WALL SECTION. SEC. |
| R806 OF 2010 FBC-RESIDENTIAL. |
| |
| B) REVISE DOOR STRUCTURAL BUCK DETAIL. REVISE SIZE AND |
| REVISE DETAIL TO SHOW FULL SUPPORT TO THE DOOR FRAME AS |
| REQUIRED BY SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL. |
| |
| C) SIZE OF WINDOW SHOWN ON THE LEFT ELEVATION DOESN'T |
| MATCH SIZE SPECIFIED ON THE FLOOR PLAN. REVISE AS |
| REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| D) REVISE WINDOWS AND DOORS DESIGN PRESSURES TO MATCH |
| CORRECT DESIGN PRESSURES AS SPECIFIED ON SHEET A-1 AND |
| A-5. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| |
| E) RIGHT ELEVATION DOESN'T MATCH FLOOR PLAN. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 11- SHEET A-4: |
| A) CLEARLY SPECIFY EXISTING AND PROPOSED WINDOWS AND |
| EXTERIOR DOORS. (COORDINATE WITH EXTERIOR ELEVATIONS ON |
| SHEET A-3). SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B) NEW FLOOR PLAN SHOWS "NEW BILLIARD ROOM" AND "NEW |
| PLAYROOM". PREVIOUS PLANS SHOWED THESE ROOMS AS |
| BEDROOMS. IT'S NOT CLEAR WHY THE ROOMS WERE REDESIGNED |
| AS PLAYROOMS, BUT IF THE ROOMS ARE NOT DESIGNED AS |
| BEDROOMS, THEN ENGINEER OF RECORD TO SPECIFY ON PLANS |
| THAT THESE ROOMS CAN NOT BE USED FOR SLEEPING PURPOSES. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 12- SHEET A-5: |
| A) THIS IS NOT ALTERATION LEVEL 2. REVISE AS REQUIRED. |
| SEE SEC.401.4 OF 2010 FBC-EXISTING BUILDING. |
| |
| B) ROOF FRAMING PLAN IS MISSING INFORMATION: (1) |
| PROVIDE WALL SECTION SHOWING WHERE IS THE NEW 2X8 WOOD |
| LEDGER GOING TO BE ATTACHED TO THE EXISTING BUILDING. |
| (2) SPECIFY LEDGER ANCHOR BOLT SIZE AND SPACING. (3) |
| SPECIFY CEILING CLEARANCES. (4) SPECIFY BEAM SIZE. (5) |
| SPECIFY ROOF PITCH. (6) SPECIFY ROOF SHEATHING SIZE AND |
| FASTENER TYPE AND SPACING. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) EXTERIOR DOORS AS SHOWN ON PLANS. |
| |
| B) ROOF SHINGLES. NOA 11-0913.10 SUBMITTED WAS THE |
| APPROVAL FOR ANOTHER PROJECT AND WAS REVIEWED AND |
| APPROVED BY ANOTHER ENGINEER NOT THE ONE RESPONSIBLE |
| FOR THIS PROJECT. AND NEED 2 COPIES. ONLY 1 WAS |
| SUBMITTED. |
| |
| C) OVERHEAD GARAGE DOOR. NEED PRODUCT APPROVAL FOR SIZE |
| OF GARAGE DOOR SPECIFIED ON PLANS. ALSO, NOA 12-0125.20 |
| SUBMITTED IS FOR ANOTHER PERMIT AND WAS APPROVED BY |
| ANOTHER ENGINEER NOT THE ONE RESPONSIBLE FO THIS |
| PROJECT. |
| |
| D) SINGLE HUNG WINDOW. NOA 11-1013.14 SUBMITTED IS NOT |
| LEGIBLE. |
| |
| E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| FRAMING PLANS AND ALL DETAILS. OR SPECIFY THE FLORIDA |
| PRODUCT APPROVAL NEXT TO THE SPECIFIED CONNECTOR. |
| FLORIDA PRODUCT APPROVAL WAS SUBMITTED FOR SOME |
| CONNECTORS, BUT NOT ALL OF THEM. |
| |
| 14- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| NOTE: ENGINEER TO CLARIFY WHY THE SIGNATURE ON THE |
| APPROVED PRODUCT APPROVALS IS DIFFERENT THAT THE |
| SIGNATURE ON THE PLANS. PROVIDE SIGNED AND SEALED |
| LETTER WITH EXPLANATION. CHAPTER 471 F.S. |
| |
| 15- ENGINEER IS USING OLD SEAL. NEED TO USE CURRENT |
| SEAL WITH THE WORDING "LICENSE" NOT "CERTIFICATE". SEC. |
| 61G15-23.001. F.A.C. |
| |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |