2014-11-13 10:50:37DATE:11/13/14
 PROJECT: 3721 EASTVIEW
 PERMIT#: 14061326
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PLANS AND NOTES ARE CONFLICTING. THE NOTES AND
 APPLICATION INDICATE ELECTRICAL SCOPE CONFORMING TO ALL
 CURRENT FBC AND NEC BUT THE EDITIONS OF THE CODES NOTED
 ARE NOT ACCURATE. THE PLANS WILL BE REVIEWED UNDER THE
 2010 FBC AND THE 2008 NEC. THE SCOPE OF WORK ON THE
 APLICATION AND THE SCOPE OF WORK THAT APPEARS TO BE
 PROPOSED ON THE PLANS SUBMITTED ARE CONFLICTING. THE
 APPLICATION STATES THAT ONLY REPAIRS ARE TO BE
 PERFORMED INVOLVING 3 SHEETS OF DRYWALL ALONG WITH SOME
 TILE AND PAINT. THE PLANS INDICATE A NEW ELECTRICAL
 PANEL, NEW A/C, SEVERAL NEW OUTLETS, CEILING FANS, AND
 LIGHTS. PLEASE ADDRESS ALL COMMENTS REGARDING THE PALNS
 SUBMITTED.
  
 2) A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.)
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE. NEC 210.52(C)(1)
  
 3) PROVIDE AN ELECTRICAL RISER DIAGRAM INDICATING SIZE,
 TYPE AND LOCATION OF THE SERVICE ENTRANCE,
 DICONNECT(S), FEEDERS, GROUNDING ELECTRODE SYSTEM,
 MAIN(S), AND PANEL(S).
  
 4) AN INTER-SYSTEM BONDING TERMINATION FOR CONNECTING
 INTER-SYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED
 FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
 ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES. NEC 250.94.
  
 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9 A FAULT CURRENT CALCULATION IS
 REQUIRED.
  
 6) THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT
 BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH
 CIRCUITS SUPPLIED. NEC 220.40. PROVIDE A LOAD
 CALCULATION IN COMPLIANCE WITH NEC ARTICLE 220 ACTUAL
 LOAD CALCULATION REQUIRED BASED ON THE NEC ARTICLE 220.
 220.1 SCOPE. THIS ARTICLE PROVIDES REQUIREMENTS FOR
 CALCULATING BRANCH-CIRCUIT, FEEDER, AND SERVICE LOADS.
 PART I PROVIDES FOR GENERAL REQUIREMENTS FOR
 CALCULATION METHODS. PART II PROVIDES CALCULATION
 METHODS FOR BRANCH-CIRCUIT LOADS. PARTS III AND IV
 PROVIDE CALCULATION METHODS FOR FEEDERS AND SERVICES.
 FABRICATING A TOTAL CONNECTED ELECTRICAL DEMAND BASED
 ON A PARTIAL PANEL SCHEDULE IS NOT AN APPROVED METHOD.
 ADDITIONALLY INCLUDE A LOAD FOR THE REAR BUILDING.
  
 7) FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL SWITCH?
 CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED TO
 PROVIDE ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR
 ENTRANCES OR EXIT SWITH GRADE LEVEL ACCESS. A VEHICLE
 DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN OUTDOOR
 ENTRANCE OR EXIT.. NEC 210.70(A)(2) INDICATE ALL
 REQUIRED SWITCHES AND LIGHTS REQUIRED.
  
 8) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11(C)(2)
  
 9) FOR ATTICS, UNDERFLOOR SPACES, UTILITY ROOMS, AND
 BASEMENTS, AT LEAST ONE LIGHTING OUTLET CONTAINING A
 SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE
 INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR
 CONTAIN EQUIPMENT REQUIRING SERVICING. AT LEAST ONE
 POINT OF CONTROL SHALL BE AT THE USUAL POINT OF ENTRY
 TO THESE SPACES. THE LIGHTING OUTLET SHALL BE PROVIDED
 AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. NEC
 210.70(3)
  
 10) PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR
 MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES.
 NEC 110.33(B)
  
 11) DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT
 FROM AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING
 OR REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS
 SHALL BE PERMITTED TO BE INSTALLED ON OR WITHIN THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14
  
 12) INDICATE ALL CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORRESPONDING TO THE REQUIRED CIRCUIT IN THE PANEL
 SCHEDULE.
  
 THE ABOVE LISTED NOTES ONLY NAME A FEW. IF THE INTENT
 OF THIS PERMIT APPLICATION AND ASSOCIATED CONSTRUCTION
 DOCUMENTS IS TO COMPLY WITH THE PROVISIONS OF ALL
 CURRENT CODES AND ORDINANCES PLEASE REVISE PLANS TO
 COMPLY WITH THE PROVISIONS OF THE 2008 EDITION OF THE
 NATIONAL ELECTRICAL CODE, THE 2010 EDITION OF THE
 FLORIDA BUILDING CODE AS WELL AS THE WEST PALM BEACH
 AMENDMENTS TO CHAPTER ONE OF THE FLORIDA BUILDING CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM, SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6717 OR [email protected]
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]