2014-11-07 07:30:20 | RESIDENTIAL (R3) ALTERATION THIRD BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| ***NOTE: THESE COMMENTS APPLY TO FRONT BUILDING ONLY. |
| REAR BUILDING COMMENTS ARE UNDER PERMIT #14061324. |
| |
| 1- SCOPE OF WORK IS NOT CLEAR. SCOPE OF WORK SPECIFIED |
| ON SHEET A-1 DOESN'T REFLECT WHAT THE FLOOR PLANS SHOW |
| AND WHAT THE PERMIT APPLICATION SPECIFIES. REVISE ALL L |
| THE INFORMATION AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| AMENDMENTS TO FBC. |
| |
| 2- REVISE VALUATION ON THE PERMIT APPLICATION TO MATCH |
| ALL THE SCOPE OF WORK SPECIFIED IN THE REVISED |
| INFORMATION REQUESTED ON ITEM #1 ABOVE. SEC. 109.3 CITY |
| AMENDMENTS TO FBC. |
| |
| 3- ENGINEER TO PROVIDE COMPLETE INFORMATION FOR THE NEW |
| STAIRS AT THE BOTTOM RIGHT SIDE SHOWN ON THE ELECTRICAL |
| PLAN. PROVIDE COMPLETE FRAMING DETAILS AND |
| SPECIFICATIONS FOR NEW DOOR, INCLUDING SIZE. PROVIDE |
| COMPLETE DETAILS AND SPECIFICATIONS FOR THE NEW STAIRS |
| SHOWING COMPLIANCE WITH SEC. R311.3 OF 2010 FBC- |
| RESIDENTIAL. INCLUDE THE REQUIRED LANDING AND RISER AND |
| TREADS DIMENSIONS. |
| |
| 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) ANY NEW DOORS OR EXTERIOR DOORS TO BE REPLACED. |
| B) ANY NEW WINDOWS OR WINDOWS TO BE REPLACED. |
| C) ALL STRUCTURAL CONNECTORS SPECIFIED ON THE FRAMING |
| DETAILS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE |
| AND PAGE SHOWING THE SPECIFIED CONNECTOR. |
| D) WINDOW MULLIONS, IF USED. |
| E) ROOF SHINGLES IF THIS SCOPE OF WORK IS GOING TO BE |
| INCLUDED. |
| |
| ***NOTE: THERE WERE SOME PRODUCT APPROVALS THAT WERE |
| INLCUDED IN THIS PACKAGE. THEY HAD A DIFFERENT PERMIT |
| NUMBER STAMPED ON THE FRONT COVER. THEY WERE ROUTED TO |
| R12 SHELF TO RIDE ALONG WITH THAT PERMIT APPLICATION. |
| |
| 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS |
| TO FBC. |
| |
| 6- IF REPLACING BEDROOM WINDOWS, THEN SPECIFY EXISTING |
| WINDOW TYPE AND SIZE AND PROPOSED WINDOW TYPE AND SIZE |
| TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENT OF |
| SEC. 604 OF 2010 FBC-EXISTING BUILDING. |
| |
| 7- IF REPLACING DOOR AND WINDOWS, THEN CLEARLY IDENTIFY |
| ON PLANS WHICH DOORS AND WINDOWS ARE GOING TO BE |
| REPLACED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| |
| ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |