Plan Review Notes
Plan Review Notes For Permit 14061326
Permit Number 14061326
Review Stop P
Sequence Number 2
Notes
Date Text
2015-07-08 05:25:231) I AM THOROGHLY CONFUSED AS TO THE SCOPE OF PLUMBING
 WORK BEING DONE AND TO WHICH STRUCTURE.
 NOTHING ON THE PLANS MATCH FOR THE PLUMBING. THE
 SANITARY RISER DIAGRAMS ON THE PLANS AND THE ONES ON
 THE 8 1/2 X 11 SHEETS DO NOT MATCH THE FLOOR PLANS.
 IDENTIFY ON THE RISER DIAGRAMS TO WHICH BULDING THEY
 APPLY. I CANNOT COMPLETE MY REVIEW UNTIL A SET OF PLANS
 ARE SUBMITTED THAT CLEARY REFLECT THE COMPLETE SCOPE OF
 PLUMBING WORK TO BE DONE. WPB AMEND. TO 201 FBC
 SEC.107.2.1.
 2) THE PLANS SHOW BUILDING #2 AS A GARAGE YET THERE IS
 A PLUMBING RISER THAT SHOWS PLUMBING FIXTURES.
 CLARIFY.WPB AMEND. TO 201 FBC SEC.107.2.1.
 3) IDENTIFY ON EACH FLOOR PLAN WHICH BUILDING NUMBER IT
 IS.WPB AMEND. TO 201 FBC SEC.107.2.1.
 4) THE LAYOUT OF THE FIXTURES ON THE RISER DIAGRAMS DO
 NOT CORRELATE WITH THE FLOOR PLAN.WPB AMEND. TO 201 FBC
 SEC.107.2.1.
 5) THEWASHING MACHINE IN THE LAUNDRY IS NOT SHOWN ON
 ANY OF THE PLUMBING RISERS.WPB AMEND. TO 201 FBC
 SEC.107.2.1.
 I SUGGEST CALLING ME TO SET UP AN APPOINTMENT TO GO
 OVER THE COMMENTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692