2014-07-30 11:53:54 | DATE: 7/30/2014 |
| PROJECT: 3721 EASTVIEW |
| PERMIT#: 14061326 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) SEE BUILDING REVIEW COMMENTS. NO PLANS SUBMITTED. |
| 2) SCOPE OF WORK AND VALUATION ON APPLICATION DOES NOT |
| MATCH REVOKED EXPIRED PERMIT APPLICATION AND PLANS FOR |
| AFTER THE FACT PROJECT. REVISE PERMIT VALUATION. FBC |
| WPB AMENDMENTS. 109.3 |
| |
| BUILDING COMMENTS BY JULIO GOMEZ: |
| "1- NO PLANS WERE SUBMITTED SHOWING SCOPE OF WORK. |
| PROVIDE COMPLETE INFORMATION FOR REVIEW. SEC. 107.2.1 |
| CITY AMENDMENTS TO FBC. ***NOTE: COORDINATE WITH ITEM |
| #2 BELOW. |
| 2- IT LOOKS LIKE THIS PERMIT WAS APPLIED FOR TO REVOKE |
| EXPIRED PERMIT APPLICATION #10110532. PERMIT |
| APPLICATION #10110532 WAS NEVER APPROVED BECAUSE |
| COMMENTS WERE NEVER ADDRESSED. PLEASE REVISE SCOPE OF |
| WORK TO MATCH SCOPE OF WORK SUBMITTED ON PERMIT |
| APPLICATION #10110532. THE FOLLOWING IS THE SCOPE OF |
| WORK FOR PERMIT APPLICATION #10110532: "MAIN HOUSE - |
| RENOVATION / REPAIRS. ELECTRIC, SHEETROCK, STUCCO, |
| CLOSE 2 WINDOWS & 1 DOOR WITH LATHE/STUCCO. INSTALL NEW |
| DOOR ON NORTH SIDE & REAR DOOR. ROOF SHINGLES, HVAC AIR |
| HANDLER & COMPRESSOR". SEC. 107.2.1 CITY AMENDMENTS TO |
| FBC." |
| 3- REVISE VALUATION TO REFLECT ALL THE SCOPE OF WORK. |
| VALUATION TO INCLUDE ALL LABOR AND MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS TO FBC." |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |
| |
| |
| |