2015-07-09 16:04:34 | 7/9/2015 |
| PROJECT: REAR STRUCTURE |
| PERMIT#: 14061324 |
| CODE: 2011EDITION OF THE NEC, FIFTH EDITION OF THE FBC |
| , WPB AMENDMENTS TO THE FBC, CHAPTER 1, ADMINISTRATION, |
| FBC SUPPLEMENTS. |
| 5TH ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) MAKE CORRECTIONS TO THE ELECTRICAL RISER DIAGRAM ON |
| PG A-4. INDICATE THE SIZE AND TYPE AND LOCATION OF THE |
| UTILITY SERVICE ENTRANCE. IS IT O/H OR U/G? |
| |
| 2) THERE IS AN INDICATION OF TWO PANEL?C? ON THE FLOOR |
| PLAN. ONE IN THE KITCHEN OF THE REAR STRUCTURE AND THE |
| OTHER IN THE CONNECTED GARAGE? CLARIFY THE ACTUAL PANEL |
| NAMES AND LOACTIONS. REVISE THE RISER DIAGRAM TO MATCH. |
| |
| 3) PG A-5 INDICATES THE DEMOLITION AND REMOVAL OF A |
| PANEL FROM A BATHROOM WALL THAT IS BEING DEMOLISHED. |
| THE NEW FLOOR PLAN LAYOUT DOES NOT INCLUDE AN |
| ELECTRICAL PANEL. HOWEVER THE RISER DIAGRAM INDICATES A |
| FEEDER TO A SUB PANEL IN THAT LOCATION. PLEASE CLARIFY |
| AND INDICATE THE LOCATION OF THE RELOCATED PANEL. |
| |
| 4) THERE ARE 3 100AMP BREAKERS INDICATED IN THE 300AMP |
| MAIN PANEL. ONE SUB FEED INDICATES A ?? PVC CONDUIT |
| WITH 3 #3 WIRES. THERE ARE SEVERAL ISSUES WITH THIS. 1. |
| IT?S NOT POSSIBLE TO BE A ?? CONDUIT. 2. IF IT?S A PVC |
| CONDUIT IT REQUIRES A GROUND WIRE FROM NEC 250.122. AND |
| 3. IT CALLS OUT A THHN CONDUCTORS. THHN IS NOT APPROVED |
| FOR WET LOCATION. AN OUTDOOR CONDUIT IS CONSIDERED A |
| WET LOCATION. |
| |
| 5) PROVIDE PANEL SCHEDULE FOR EACH OF THESE PANELS. NEC |
| 408.4 |
| |
| 6) THERE ARE SIMILAR ISSUES WITH THE NEXT CONDUIT TO |
| THE NEW 100AMP SUB PANEL ?C?. THE RISER DIAGRAM SHOWS A |
| 1? CONDUIT 3,#6 AND 1#10CU GRD. A #6 CU CONDUCTOR IS |
| NOT APPROVED FOR A 100AMP OCPD. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |