Date Text
2015-07-09 16:04:347/9/2015
 PROJECT: REAR STRUCTURE
 PERMIT#: 14061324
 CODE: 2011EDITION OF THE NEC, FIFTH EDITION OF THE FBC
 , WPB AMENDMENTS TO THE FBC, CHAPTER 1, ADMINISTRATION,
 FBC SUPPLEMENTS.
 5TH ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) MAKE CORRECTIONS TO THE ELECTRICAL RISER DIAGRAM ON
 PG A-4. INDICATE THE SIZE AND TYPE AND LOCATION OF THE
 UTILITY SERVICE ENTRANCE. IS IT O/H OR U/G?
  
 2) THERE IS AN INDICATION OF TWO PANEL?C? ON THE FLOOR
 PLAN. ONE IN THE KITCHEN OF THE REAR STRUCTURE AND THE
 OTHER IN THE CONNECTED GARAGE? CLARIFY THE ACTUAL PANEL
 NAMES AND LOACTIONS. REVISE THE RISER DIAGRAM TO MATCH.
  
 3) PG A-5 INDICATES THE DEMOLITION AND REMOVAL OF A
 PANEL FROM A BATHROOM WALL THAT IS BEING DEMOLISHED.
 THE NEW FLOOR PLAN LAYOUT DOES NOT INCLUDE AN
 ELECTRICAL PANEL. HOWEVER THE RISER DIAGRAM INDICATES A
 FEEDER TO A SUB PANEL IN THAT LOCATION. PLEASE CLARIFY
 AND INDICATE THE LOCATION OF THE RELOCATED PANEL.
  
 4) THERE ARE 3 100AMP BREAKERS INDICATED IN THE 300AMP
 MAIN PANEL. ONE SUB FEED INDICATES A ?? PVC CONDUIT
 WITH 3 #3 WIRES. THERE ARE SEVERAL ISSUES WITH THIS. 1.
 IT?S NOT POSSIBLE TO BE A ?? CONDUIT. 2. IF IT?S A PVC
 CONDUIT IT REQUIRES A GROUND WIRE FROM NEC 250.122. AND
 3. IT CALLS OUT A THHN CONDUCTORS. THHN IS NOT APPROVED
 FOR WET LOCATION. AN OUTDOOR CONDUIT IS CONSIDERED A
 WET LOCATION.
  
 5) PROVIDE PANEL SCHEDULE FOR EACH OF THESE PANELS. NEC
 408.4
  
 6) THERE ARE SIMILAR ISSUES WITH THE NEXT CONDUIT TO
 THE NEW 100AMP SUB PANEL ?C?. THE RISER DIAGRAM SHOWS A
 1? CONDUIT 3,#6 AND 1#10CU GRD. A #6 CU CONDUCTOR IS
 NOT APPROVED FOR A 100AMP OCPD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.