Plan Review Notes For Permit 14061324 |
Permit Number |
14061324 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2015-07-08 05:24:32 | 1) I AM THOROGHLY CONFUSED AS TO THE SCOPE OF PLUMBING | | WORK BEING DONE AND TO WHICH STRUCTURE. | | NOTHING ON THE PLANS MATCH FOR THE PLUMBING. THE | | SANITARY RISER DIAGRAMS ON THE PLANS AND THE ONES ON | | THE 8 1/2 X 11 SHEETS DO NOT MATCH THE FLOOR PLANS. | | IDENTIFY ON THE RISER DIAGRAMS TO WHICH BULDING THEY | | APPLY. I CANNOT COMPLETE MY REVIEW UNTIL A SET OF PLANS | | ARE SUBMITTED THAT CLEARY REFLECT THE COMPLETE SCOPE OF | | PLUMBING WORK TO BE DONE. WPB AMEND. TO 201 FBC | | SEC.107.2.1. | | 2) THE PLANS SHOW BUILDING #2 AS A GARAGE YET THERE IS | | A PLUMBING RISER THAT SHOWS PLUMBING FIXTURES. | | CLARIFY.WPB AMEND. TO 201 FBC SEC.107.2.1. | | 3) IDENTIFY ON EACH FLOOR PLAN WHICH BUILDING NUMBER IT | | IS.WPB AMEND. TO 201 FBC SEC.107.2.1. | | 4) THE LAYOUT OF THE FIXTURES ON THE RISER DIAGRAMS DO | | NOT CORRELATE WITH THE FLOOR PLAN.WPB AMEND. TO 201 FBC | | SEC.107.2.1. | | 5) THEWASHING MACHINE IN THE LAUNDRY IS NOT SHOWN ON | | ANY OF THE PLUMBING RISERS.WPB AMEND. TO 201 FBC | | SEC.107.2.1. | | I SUGGEST CONTACTING ME TO SET UP AN APPOINTMENT TO GO | | OVER THE COMMENTS. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|