2015-04-28 16:04:36DATE:4/28/2015
 PROJECT: 3721 EASTVIEW REAR STRUCTURE
 PERMIT#: 14061324
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 4TH ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 SEE BUILDING COMMENTS AS WELL.
  
 1) PROVIDE A LOAD SUMMARY. NEC 220.16
  
 2) PROVIDE AN ELECTRICAL RISER DIAGRAM INDICATING SIZE,
 TYPE AND LOCATION OF THE SERVICE ENTRANCE,
 DISCONNECT(S), FEEDERS, GROUNDING ELECTRODE SYSTEM,
 MAIN(S), AND PANEL(S).
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9 A FAULT CURRENT CALCULATION IS
 REQUIRED.
  
 4) VERIFY RECEPTACLE SPACING. NEC 210.52
  
 5) INDICATE ALL CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORRESPONDING TO THE REQUIRED CIRCUIT IN THE PANEL
 SCHEDULE.
  
 6) PROVIDE A CIRCUIT DIRECTORY FOR EACH PANEL AND
 SUB-PANEL. EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL
 BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,