Plan Review Notes For Permit 14061324 |
Permit Number |
14061324 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2015-04-28 16:04:36 | DATE:4/28/2015 | | PROJECT: 3721 EASTVIEW REAR STRUCTURE | | PERMIT#: 14061324 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 4TH ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | SEE BUILDING COMMENTS AS WELL. | | | | 1) PROVIDE A LOAD SUMMARY. NEC 220.16 | | | | 2) PROVIDE AN ELECTRICAL RISER DIAGRAM INDICATING SIZE, | | TYPE AND LOCATION OF THE SERVICE ENTRANCE, | | DISCONNECT(S), FEEDERS, GROUNDING ELECTRODE SYSTEM, | | MAIN(S), AND PANEL(S). | | | | 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS | | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT | | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | INTERRUPTED. NEC 110.9 A FAULT CURRENT CALCULATION IS | | REQUIRED. | | | | 4) VERIFY RECEPTACLE SPACING. NEC 210.52 | | | | 5) INDICATE ALL CIRCUIT NUMBERS ON THE FLOOR PLAN | | CORRESPONDING TO THE REQUIRED CIRCUIT IN THE PANEL | | SCHEDULE. | | | | 6) PROVIDE A CIRCUIT DIRECTORY FOR EACH PANEL AND | | SUB-PANEL. EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL | | BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND | | SPECIFIC PURPOSE OR USE. NEC 408.4 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|