2015-04-13 12:48:53RESIDENTIAL (R3) ALTERATION/ ADDITION FOURTH BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 NOTE: THESE COMMENTS APPLY TO FRONT AND REAR BUILDINGS.
 DRAWINGS A-1 TO A-5 SUBMITTED:
  
 1- SITE PLAN SHOWN ON SHEET A-1 DOESN'T MATCH SITE PLAN
 SHOWN ON SHEET A-5. AND IS MISSING THE CONNECTION
 (LAUNDRY ROOM) OF THE GARAGE WITH THE REAR BUILDING.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- SCOPE OF WORK SPECIFIED ON SHEET A-1 DOESN'T MATCH
 SCOPE OF WORK SPECIFIED ON SHEET A-5. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 3- DESIGN DATA FOR WIND LOADS SHOWN ON SHEET A-1
 DOESN'T MATCH DESIGN DATA SPECIFIED ON SHEET A-5. SEC.
 107.2.1 CITY AMENDMENTS.
  
 4- INFORMATION SHOWN ON THE DESIGN DATA ON SHEET A-1
 AND SHEET A-5 IS CONFUSING. INFORMATION FOR INTERIOR
 AND END ZONE IS REPEATED TWICE BUT THE DESIGN PRESSURES
 ARE DIFFERENT. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES FEES. PROVIDE COPY OF SIGNED CONTRACT
 THAT DESCRIBES ALL THE SCOPE OF WORK. SEC. 109.3 CITY
 AMENDMENTS.
  
 6- SHEET A-1:
 A) PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE NEW ATTIC ACCESS WITH
 LADDER.
  
 B) ENGINEER OF RECORD TO SPECIFY THE ALTERATION LEVEL
 TYPE OR COMBINATION OF LEVELS OF ALTERATION AS REQUIRED
 BY SEC. 401.4 OF 2010 FBC-EXISTING BUILDING.
  
 C) CLEARLY SPECIFY WHICH WINDOWS AND EXTERIOR DOORS ARE
 EXISTING AND WHICH ARE GOING TO BE REPLACED. IF
 REPLACING EXISTING BEDROOM WINDOWS, THEN SPECIFY
 EXISTING TYPE AND SIZE AND PROPOSED TYPE AND SIZE TO
 VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC.
 604 OF 2010 FBC-EXISTING BUILDING.
  
 7- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 8- COORDINATE LABELING NUMBERS OF BUILDINGS SHOWN ON
 THE SITE PLAN WITH LABELING OF BUILDINGS SHOWN ON
 SHEETS A-2 TO A-5. REVISE AS REQUIRED. CLEARLY MATCH
 BUILDING #1, BUILDING #2 AND BUILDING #3 WITH NUMBERS
 SHOWN ON THE SITE PLAN. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- SHEET A-2:
 A) PROVIDE GARAGE DOOR COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE STAIRS, HANDRAILS AND GUARDRAIL THAT MATCHES
 NEW PORCH ON SHEET A-5. PROVIDE COMPLETE FRAMING
 DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 LIVE LOADS OF TABLE R301.5 OF 2010 FBC-RESIDENTIAL.
 SPECIFY ALL FRAMING MEMBERS AND FASTENERS.
  
 C) INFORMATION SHOWN ON THE WOOD FRAMING DETAIL
 SECTION, WALL SECTION AND DOOR FRAMING SECTION DOESN'T
 MATCH. REVISE AS REQUIRED TO MATCH AND CLARIFY WHERE
 ARE THESE SECTIONS TAKEN AT. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 10- SHEET A-3:
 A) WALL SECTION A/A-1: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW PROVIDING "CROSS VENTILATION
 IN BLOCKING" AS SPECIFIED ON THE WALL SECTION. SEC.
 R806 OF 2010 FBC-RESIDENTIAL.
  
 B) REVISE DOOR STRUCTURAL BUCK DETAIL. REVISE SIZE AND
 REVISE DETAIL TO SHOW FULL SUPPORT TO THE DOOR FRAME AS
 REQUIRED BY SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL.
  
 C) SIZE OF WINDOW SHOWN ON THE LEFT ELEVATION DOESN'T
 MATCH SIZE SPECIFIED ON THE FLOOR PLAN. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 D) REVISE WINDOWS AND DOORS DESIGN PRESSURES TO MATCH
 CORRECT DESIGN PRESSURES AS SPECIFIED ON SHEET A-1 AND
 A-5. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 E) RIGHT ELEVATION DOESN'T MATCH FLOOR PLAN. SEC.
 107.2.1 CITY AMENDMENTS.
  
 11- SHEET A-4:
 A) CLEARLY SPECIFY EXISTING AND PROPOSED WINDOWS AND
 EXTERIOR DOORS. (COORDINATE WITH EXTERIOR ELEVATIONS ON
 SHEET A-3). SEC. 107.2.1 CITY AMENDMENTS.
  
 B) NEW FLOOR PLAN SHOWS "NEW BILLIARD ROOM" AND "NEW
 PLAYROOM". PREVIOUS PLANS SHOWED THESE ROOMS AS
 BEDROOMS. IT'S NOT CLEAR WHY THE ROOMS WERE REDESIGNED
 AS PLAYROOMS, BUT IF THE ROOMS ARE NOT DESIGNED AS
 BEDROOMS, THEN ENGINEER OF RECORD TO SPECIFY ON PLANS
 THAT THESE ROOMS CAN NOT BE USED FOR SLEEPING PURPOSES.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 12- SHEET A-5:
 A) THIS IS NOT ALTERATION LEVEL 2. REVISE AS REQUIRED.
 SEE SEC.401.4 OF 2010 FBC-EXISTING BUILDING.
  
 B) ROOF FRAMING PLAN IS MISSING INFORMATION: (1)
 PROVIDE WALL SECTION SHOWING WHERE IS THE NEW 2X8 WOOD
 LEDGER GOING TO BE ATTACHED TO THE EXISTING BUILDING.
 (2) SPECIFY LEDGER ANCHOR BOLT SIZE AND SPACING. (3)
 SPECIFY CEILING CLEARANCES. (4) SPECIFY BEAM SIZE. (5)
 SPECIFY ROOF PITCH. (6) SPECIFY ROOF SHEATHING SIZE AND
 FASTENER TYPE AND SPACING. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) EXTERIOR DOORS AS SHOWN ON PLANS.
  
 B) ROOF SHINGLES. NOA 11-0913.10 SUBMITTED WAS THE
 APPROVAL FOR ANOTHER PROJECT AND WAS REVIEWED AND
 APPROVED BY ANOTHER ENGINEER NOT THE ONE RESPONSIBLE
 FOR THIS PROJECT. AND NEED 2 COPIES. ONLY 1 WAS
 SUBMITTED.
  
 C) OVERHEAD GARAGE DOOR. NEED PRODUCT APPROVAL FOR SIZE
 OF GARAGE DOOR SPECIFIED ON PLANS. ALSO, NOA 12-0125.20
 SUBMITTED IS FOR ANOTHER PERMIT AND WAS APPROVED BY
 ANOTHER ENGINEER NOT THE ONE RESPONSIBLE FO THIS
 PROJECT.
  
 D) SINGLE HUNG WINDOW. NOA 11-1013.14 SUBMITTED IS NOT
 LEGIBLE.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 FRAMING PLANS AND ALL DETAILS. OR SPECIFY THE FLORIDA
 PRODUCT APPROVAL NEXT TO THE SPECIFIED CONNECTOR.
 FLORIDA PRODUCT APPROVAL WAS SUBMITTED FOR SOME
 CONNECTORS, BUT NOT ALL OF THEM.
  
 14- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: ENGINEER TO CLARIFY WHY THE SIGNATURE ON THE
 APPROVED PRODUCT APPROVALS IS DIFFERENT THAT THE
 SIGNATURE ON THE PLANS. PROVIDE SIGNED AND SEALED
 LETTER WITH EXPLANATION. CHAPTER 471 F.S.
  
 15- ENGINEER IS USING OLD SEAL. NEED TO USE CURRENT
 SEAL WITH THE WORDING "LICENSE" NOT "CERTIFICATE". SEC.
 61G15-23.001. F.A.C.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
2015-04-09 11:46:231) I AM THOROGHLY CONFUSED AS TO THE SCOPE OF PLUMBING
 WORK BEING DONE AND TO WHICH STRUCTURE.
 NOTHING ON THE PLANS MATCH FOR THE PLUMBING. THE
 SANITARY RISER DIAGRAMS ON THE PLANS AND THE ONES ON
 THE 8 1/2 X 11 SHEETS DO NOT MATCH THE FLOOR PLANS.
 IDENTIFY ON THE RISER DIAGRAMS TO WHICH BULDING THEY
 APPLY. I CAN COMPLETE MY REVIEW UNTIL A SET OF PLANS
 ARE SUBMITTED THAT CLEARY REFLECT THE COMPLETE SCOPE OF
 PLUMBING WORK TO BE DONE. WPB AMEND. TO 201 FBC
 SEC.107.2.1.
  
 PLUMBING PLAN REVIEW