Plan Review Notes
Plan Review Notes For Permit 14061324
Permit Number 14061324
Review Stop E
Sequence Number 3
Notes
Date Text
2014-11-13 10:10:40DATE:11/13/14
 PROJECT: 3721 EASTVIEW
 PERMIT#: 14061324
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PLANS AND NOTES ARE CONFLICTING. THE NOTES AND
 APPLICATION INDICATE ELECTRICAL SCOPE CONFORMING TO ALL
 CURRENT FBC AND NEC BUT THE EDITIONS OF THE CODES NOTED
 ARE NOT ACCURATE. THE PLANS WILL BE REVIEWED UNDER THE
 2010 FBC AND THE 2008 NEC. THE SCOPE OF WORK ON THE
 APLICATION AND THE SCOPE OF WORK THAT APPEARS TO BE
 PROPOSED ON THE PLANS SUBMITTED ARE CONFLICTING. THE
 APPLICATION STATES THAT ONLY INTERIOIR FINISH ARE TO BE
 PERFORMED INVOLVING A/C, ELECTRIC, DRYWALL, TILE, AND
 PAINT. THE PLANS FOR THE REAR BUILDING INDICATE DEMO
 ONLY WITH A NEW GARAGE DOOR AND A GFI OUTLET. PLEASE
 ADDRESS ALL COMMENTS REGARDING THE PALNS SUBMITTED.
  
 2) THE DEMOLITION PLAN INDICATES AN ELECTRICAL PANEL.
 THE NEW FLOOR PLAN HAS NO ELECTRICAL PANEL. PROVIDE
 INFORMATION TO CLARIFY WHERE AND HOW THE DEMOLISHED
 FEEDER IS TERMINATED AND WHERE AND HOW THE NEW BRANCH
 CIRCUIT COMES FROM TO FEED THE NEW GFI OUTLET.
  
 3) AT LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER.
 INDICATE THE REQUIRED LIGHTING OUTLET. NEC 210.70(2))A)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM, SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND
 LEAVE THE PREVIOUSLY REVIEWED SHEETS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.