2015-07-06 14:51:56NOTE: THESE COMMENTS APPLY TO FRONT AND REAR BUILDINGS.
 DRAWINGS A-1 TO A-5 SUBMITTED ARE FOR BOTH STRUCTURES:
  
 1- CLARIFY WHERE IS THE GAF MINERAL GUARD RESIDENTIAL
 ROLL ROOFING UNDERLAYMENT (NOA 13-1104.03) SUBMITTED
 GOING TO BE INSTALLED? SEC. 107.2.1 CITY AMENDMENTS.
  
 2- CLARIFY WHERE IS THE GAF CONVENTIONAL BUILT-UP ROOF
 SYSTEM (NOA 13-1022.15) SUBMITTED GOING TO BE
 INSTALLED?. SEC. 107.2.1 CITY AMENDMENTS. PLANS CALL
 FOR EXISTING FLAT ROOF ON REAR BUILDING. NO RE-ROOF. IF
 THIS BUILDING IS GOING TO BE RE-ROOFED, THEN NEED TO
 IDENTIFY SPECIFIC ASSEMBLY TO BE INSTALLED AND PROVIDE
 SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF THE NOA.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF SHINGLES. (REPEAT COMMENT. NO PRODUCT APPROVAL
 SUBMITTED).
  
  