Plan Review Notes
Plan Review Notes For Permit 14061311
Permit Number 14061311
Review Stop ENG
Sequence Number 1
Notes
Date Text
2014-08-22 09:31:211. PLEASE SUBMIT SIGNED AND SEALED DRAINAGE
 CALCULATIONS INCLUDING RECOVERY CALCULATIONS SINCE
 RETENTION IS PROPOSED AND THE DRAINAGE SYSTEM WILL BE
 THE CITY'S RESPONSIBILITY TO MAINTAIN.
  
 2. REVISE THE PLANS TO INCLUDE DETAILS FOR THE
 CONNECTION INTO THE EXISTING STORM MANHOLE
  
 3. SPECIFY COMPACTION DENSITIES UNDER THE PAVERS AND
 WITHIN THE DRY RETENTION AREAS ,
  
 4. GRADES ARE TO REFERENCED NGVD PER SECTION 78-9 OF
 THE CITY'S CODE OF ORDINANCES. NOTE 6 ON SHEET C-2
 REFERENCES NAVD 88.
  
 5. ENGINEERING DEPARTMENT DEVELOPMENT APPROVAL AND
 RIGHT-OF-WAY PERMIT ARE REQUIRED PRIOR TO THE START OF
 CONSTRUCTION.