Plan Review Notes For Permit 14061310 |
Permit Number |
14061310 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-07-02 14:09:42 | DATE: 7/2/2014 | | PROJECT: ACCESS CONTROL | | PERMIT#: 14061310 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | DUPLICATE COMMENTS. THE PLAN IS DENIED FOR THE SAME | | REASON PETER LEDUC, FIRE MARSHAL DENIED IT. SEE | | FOLLOWING COMMENTS. | | | | THE PLAN IS TOO SMALL AND UNREADABLE. FBC 107.2.1 | | | | THE LOCATION OF THE ACS CANNOT BE DETERMINED. | | | | THE TYPE OF ACS IS NOT IDENTIFIED. | | | | THE EXITS SHALL NOT BE LOCKED AGAINST EGRESS AND THE | | ACS SHALL BE IN COMPLAINACE WITH CHAPTER 7 OF THE | | FLORIDA LIFE SAFETY CODE. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|